Skip to main content
Schneider Electric C63S3

Schneider C63S3 Molded Case Breaker

MPNC63S3
Active

C63S3 - NSX630S by SQUARE D

$1,189.99Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

C63S3 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeWithout protection
Product or component typeBasic frame
Voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Breaking capacity100 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 120 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 90 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Current630 A at 40 °C
Breaking capacity codeS 100 kA 415 V AC
[Ics] rated service breaking capacity100 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 120 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 90 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz

All specifications

C63S3 additional specifications
ParameterValue
Poles description3P
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting modeFixed
Mounting supportBackplate
Connection pitch45 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Electrical shock protection classClass II on front face
Depth110 mm
Width140 mm
Height255 mm
Electrical durability6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 8000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability15000 cycles conforming to IEC 60947-2
StandardsEN/IEC 60947-2 UL 60947-4-1
RangeComPacT
Device short nameNSX630S
Device applicationDistribution
Overvoltage categoryIII
Suitability for isolationYes conforming to EN/IEC 60947-2
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
MPN
C63S3