Skip to main content
Schneider Electric C63W35E630 — Miniature Circuit Breakers (MCB)

Schneider Electric C63W35E630 ComPacT NSX 630A, 100kA at 690

MPNC63W35E630
Active

Schneider Electric ComPacT NSX, C63W35E630, 3P, 630 A, MicroLogic 5.3 E electronic trip unit, 100 kA Icu at 690 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C63W35E630 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C63W35E630 — Ratings
ParameterValue
Rated current (In)630 A at 40 °C
Poles configuration3P
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C63W35E630 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C63W35E630 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C63W35E630 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C63W35E630 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C63W35E630 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range250...630 A
Trip unit protection functionsLSI

Product details

The C63W35E630 is a Schneider Electric ComPacT NSX630HB2 molded-case circuit breaker, 3-pole, rated 630 A at 40 °C, with a MicroLogic 5.3 E electronic trip unit.

Trip unit and protection

The MicroLogic 5.3 E provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection, plus integrated energy metering and power-quality data via the LCD display.

Mounting and environment

Mounts on a backplate in horizontal or vertical orientation, flat against the panel. Front connections on both line and load sides simplify bus-bar or cable routing in a distribution panel. Derate above 2000 m altitude if the installation is at elevation.

Frequently asked questions

What is the breaking capacity of C63W35E630?

The C63W35E630 has a 100 kA Icu breaking capacity at 690 V AC per IEC 60947-2, also rated 100 kA at 500 V and 525 V AC.

What trip unit does C63W35E630 use?

It uses a MicroLogic 5.3 E electronic trip unit with L, S, and I protection, plus energy metering and an LCD display.

Where can I buy C63W35E630?

The C63W35E630 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN