Skip to main content
Schneider Electric C63W45E630 — Miniature Circuit Breakers (MCB)

C63W45E630 ComPacT NSX 630A 100kA 690V AC Circuit Breaker

MPNC63W45E630
Active

Schneider Electric ComPacT NSX630HB2, 630 A, 4P, 100 kA Icu at 690 V AC, MicroLogic 5.3 E electronic trip unit, LCD display.

$23.57Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C63W45E630 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C63W45E630 — Ratings
ParameterValue
Rated current (In)630 A at 40 °C
Poles configuration4P
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C63W45E630 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C63W45E630 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C63W45E630 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C63W45E630 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C63W45E630 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range250...630 A
Trip unit protection functionsLSI

Product details

The C63W45E630 is a ComPacT NSX630HB2 moulded-case circuit breaker rated 630 A at 40 °C, with a full-rated breaking capacity of 100 kA Icu at 690 V AC 50/60 Hz per IEC 60947-2. That HB2 suffix means the frame is sized for the highest interrupting duty in the NSX line — 100 kA holds all the way from 500 V through 690 V, so you don't lose headroom on a 480 V or 600 V distribution board. Four poles, utilisation category A, with front-front connections (both line and load side accessible from the front panel).

MicroLogic 5.3 E — energy metering and thermal memory

The electronic trip unit is a MicroLogic 5.3 E, which gives you L (long-time overload), S (short-time short-circuit), and I (instantaneous) protection curves. What sets the 'E' variant apart is the integrated energy metering — it communicates demand current, power, power quality, and time-stamped event tables, so this breaker doubles as a panel-level power monitor without a separate meter. The LCD display shows local readings and LED signalling for ready-to-operate (green), 90 % Ir overload warning (orange), and 105 % Ir overload trip (red).

Active production — no obsolescence concern

Lifecycle status is current — this is an active catalogue item, not a last-time-buy or end-of-life SKU. No successor part number exists because none is needed.

Mounts on a backplate (not DIN-rail — this is a bolted-frame breaker). Accepts horizontal or vertical orientation, flat against the back. Overall dimensions: 255 mm high, 185 mm wide, 110 mm deep. Connection pitch is 45 mm per pole. Six accessory slots are available for shunt trips, aux contacts, or communication modules. Operates at 0–2000 m without derating; derate above that altitude.

Durability and environmental range

Mechanical durability is 15,000 cycles. Electrical durability depends on voltage and current: 8,000 cycles at 440 V at half rated current (In/2), 4,000 cycles at 440 V at full In, 6,000 cycles at 690 V at In/2, and 2,000 cycles at 690 V at full In. Relative humidity range 0–95 %. Standards: EN/IEC 60947-2.

Frequently asked questions

Who supplies C63W45E630 and how is it quoted for volume purchases?

C63W45E630 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is C63W45E630's listed range on this component line?

The range is ComPacT, product name ComPacT NSX, device short name NSX630HB2.

What is C63W45E630's breaking capacity at 690 V?

It is rated 100 kA Icu at 660/690 V AC 50/60 Hz per IEC 60947-2, and the same 100 kA holds at 500 V and 525 V AC.

What trip unit does C63W45E630 use and what does it measure?

It uses a MicroLogic 5.3 E electronic trip unit with L, S, I protection and integrated energy metering — it communicates demand current, power, power quality, and time-stamped event data.

MPN
C63W45E630