Skip to main content
Schneider Electric CAD32AB7 — Contactors

Schneider Electric CAD32AB7 TeSys Deca Control Relay, 3NO+2N

MPNCAD32AB7
Active

Schneider Electric TeSys Deca control relay, CAD32AB7, 3NO+2NC, ≤690V, 24V AC standard coil, snap-in terminals.

$83.28Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

CAD32AB7 — Identification
ParameterValue
Product / component typeControl relay
Series / rangeTeSys
ApplicationControl circuit
CAD32AB7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)10 MOhm
Utilisation categoryAC-15 AC-14 DC-13
CAD32AB7 — Environmental
ParameterValue
IP degree of protectionIP2X front face VDE 0106
Operating altitude0...9842.52 ft (0...3000 m)
Mechanical robustnessShocks control relay open10 Gn for 11 ms IEC 60068-2-27 Shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 Vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 Vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
Protective treatment / pollution degreeTH IEC 60068
CAD32AB7 — Approvals
ParameterValue
StandardsEN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5 JIS C8201-5-1
CAD32AB7 — Mechanical
ParameterValue
Width1.8 in (45 mm)
Height4.2 in (107 mm)
Depth3.7 in (93 mm)

Product details

The CAD32AB7 is a TeSys Deca control relay from Schneider Electric, built for switching control circuits in industrial panels. Its contact complement is 3 normally-open plus 2 normally-closed poles, rated for operational voltages up to 690 V.

The utilisation categories tell you what loads this relay can switch reliably: AC-15 for solenoid valves and electromagnetic clutches (inductive loads above 72 VA), AC-14 for contactor coils (inductive loads up to 72 VA), and DC-13 for solenoids and clutches on DC control circuits. The 24 V AC coil draws a sealed current that stays within the PLC output card's per-channel rating, provided the card is rated for AC pilot duty — verify the inrush, not just the hold-in, against the output's maximum peak current. The operating temperature range is -40 to 140 °F (-40 to 60 °C), with derating permitted up to 158 °F (70 °C). Storage range is -76 to 176 °F (-60 to 80 °C), which governs shipping and site storage, not running conditions. This is a dry-location control relay, not a contactor for motor power switching.

The CAD32AB7 carries compliance with EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1 — the full set of control-circuit device standards for North America, Europe, China, and Japan. That means the part is accepted in panels destined for UL-listed machinery, IEC-nameplate export gear, and CCC-marked equipment without a separate approval hunt.

Mechanical and environmental robustness

The relay withstands 10 Gn shock for 11 ms in the open state and 15 Gn in the closed state, per IEC 60068-2-27. Vibration resistance is 2 Gn from 5 to 300 Hz when open, 4 Gn when closed. That puts it into the range for installation on panels mounted to rotating machinery or near reciprocating compressors, provided the mounting rail is braced against resonance.

Frequently asked questions

What standards does CAD32AB7 comply with?

It complies with EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1. That covers control-circuit device requirements for Europe, North America, China, and Japan.

What is the contact configuration of CAD32AB7?

The relay has 3 normally-open and 2 normally-closed poles (3 NO + 2 NC).

What coil voltage does CAD32AB7 use?

The coil is rated for 24 V AC standard.

MPN
CAD32AB7