The CAD32ARD is a TeSys Deca control relay from Schneider Electric, built for control-circuit switching in industrial panels. It carries 3 normally-open and 2 normally-closed contacts, rated for operational voltages up to 690 V with a 440 V DC standard coil. Rated for utilisation categories AC-15, AC-14, and DC-13, so it handles solenoid loads, electromagnetic clutches, and contactor coils — the typical inductive loads you find in a control cabinet.
Approved to EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1, so it's accepted across European, North American, Chinese, and Japanese markets without additional certification work. Protective treatment conforms to TH per IEC 60068, meaning it's treated for tropical environments with high humidity and temperature cycling.
Mechanical and environmental specs
Operates from -40 to 60 °C, with derating allowed up to 70 °C. Front face carries IP2X protection per VDE 0106, so it's finger-safe when mounted in a closed panel. Rated for vibration at 2 Gn open and 4 Gn closed (5–300 Hz), and shock at 10 Gn open and 15 Gn closed — numbers that matter when the relay sits on a machine frame or near a press.