Skip to main content
Schneider Electric CAD32ARD — Contactors

Schneider TeSys CAD32ARD Control Relay, 3NO+2NC, ≤690V

MPNCAD32ARD
Active

Schneider Electric TeSys Deca control relay, CAD32ARD, 3NO+2NC, ≤690V, 440V DC standard coil, snap-in terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

CAD32ARD — Identification
ParameterValue
Product / component typeControl relay
Series / rangeTeSys
ApplicationControl circuit
CAD32ARD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)10 MOhm
Utilisation categoryAC-15 AC-14 DC-13
CAD32ARD — Environmental
ParameterValue
IP degree of protectionIP2X front face conforming to VDE 0106
Operating altitude0...3000 m
Mechanical robustnessShocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTH conforming to IEC 60068
CAD32ARD — Approvals
ParameterValue
StandardsEN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5 JIS C8201-5-1
CAD32ARD — Mechanical
ParameterValue
Width45 mm
Height107 mm
Depth93 mm
CAD32ARD — Other specifications
ParameterValue
Device short nameCAD
Pole contact composition3 NO + 2 NC
Ambient air temperature for storage-60...80 °C
Ambient air temperature for operation-40...60 °C 60...70 °C with derating

Product details

The CAD32ARD is a TeSys Deca control relay from Schneider Electric, built for control-circuit switching in industrial panels. It carries 3 normally-open and 2 normally-closed contacts, rated for operational voltages up to 690 V with a 440 V DC standard coil. Rated for utilisation categories AC-15, AC-14, and DC-13, so it handles solenoid loads, electromagnetic clutches, and contactor coils — the typical inductive loads you find in a control cabinet.

Approved to EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1, so it's accepted across European, North American, Chinese, and Japanese markets without additional certification work. Protective treatment conforms to TH per IEC 60068, meaning it's treated for tropical environments with high humidity and temperature cycling.

Mechanical and environmental specs

Operates from -40 to 60 °C, with derating allowed up to 70 °C. Front face carries IP2X protection per VDE 0106, so it's finger-safe when mounted in a closed panel. Rated for vibration at 2 Gn open and 4 Gn closed (5–300 Hz), and shock at 10 Gn open and 15 Gn closed — numbers that matter when the relay sits on a machine frame or near a press.

Frequently asked questions

What compliance documentation does Schneider provide for CAD32ARD?

The relay carries approvals to EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1, covering European, North American, Chinese, and Japanese regulatory requirements.

MPN