Skip to main content
Schneider Electric CAD32ASD — Contactors

Schneider CAD32ASD TeSys Deca Control Relay, 3NO+2NC, 72V DC

MPNCAD32ASD
Active

Schneider Electric TeSys Deca CAD32ASD control relay, 3NO+2NC, ≤690V, 72V DC standard coil, snap-in terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

CAD32ASD — Identification
ParameterValue
Product / component typeControl relay
Series / rangeTeSys
ApplicationControl circuit
CAD32ASD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)10 MOhm
Utilisation categoryAC-15 AC-14 DC-13
CAD32ASD — Environmental
ParameterValue
IP degree of protectionIP2X front face conforming to VDE 0106
Operating altitude0...3000 m
Mechanical robustnessShocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTH conforming to IEC 60068
CAD32ASD — Approvals
ParameterValue
StandardsEN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5 JIS C8201-5-1
CAD32ASD — Mechanical
ParameterValue
Width45 mm
Height107 mm
Depth93 mm
CAD32ASD — Other specifications
ParameterValue
Device short nameCAD
Pole contact composition3 NO + 2 NC
Ambient air temperature for storage-60...80 °C
Ambient air temperature for operation-40...60 °C 60...70 °C with derating

Product details

It carries a 72 V DC standard coil and terminates via snap-in terminals, which means it clips directly onto a DIN rail in the panel without needing a separate base. The utilisation categories — AC-15, AC-14, and DC-13 — tell you what loads this relay can switch reliably. AC-15 covers solenoid valves and electromagnetic clutches above 72 VA; AC-14 covers small electromagnetic loads below 72 VA; DC-13 covers solenoids and contactors on DC control circuits. So if you are replacing a relay in a 24 VDC valve manifold or a 110 VAC contactor coil circuit, this part fits.

The CAD32ASD is a panel-mount control relay from the TeSys Deca range. Its 45 mm width and 107 mm height fit the standard DIN-rail footprint alongside contactors and overloads. The IP2X front-face protection (per VDE 0106) means the live terminals are finger-safe behind the panel door — no extra shrouding needed for routine access. Operating temperature spans -40 to 60 °C, with derating allowed up to 70 °C. Storage range is -60 to 80 °C. The TH protective treatment per IEC 60068 handles tropical humidity, so this relay is fine in unheated enclosures or coastal plants.

The CAD32ASD carries EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1 approvals. That covers control-circuit devices for industrial use across North America, Europe, China, and Japan — no separate UL/CSA variant needed for a global machine build.

Frequently asked questions

What are the key ratings for the CAD32ASD?

The CAD32ASD is a 3 NO + 2 NC control relay rated for control circuits up to 690 V, with a 72 V DC coil. It is approved to EN/IEC 60947-5-1, UL 60947-5-1, and CSA C22.2 No 60947-5-1, among others.

What compliance documentation does Schneider provide for the CAD32ASD?

The CAD32ASD is certified to EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1. These cover the main industrial safety and performance standards for control-circuit devices.

MPN
CAD32ASD