It carries a 72 V DC low consumption coil and snap-in terminals for panel wiring. Rated for utilisation categories AC-15, AC-14, and DC-13 per EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1 — so it handles solenoid and electromagnetic loads in control circuits across global installations.
Dimensions are 45 mm wide, 107 mm high, and 93 mm deep — a standard TeSys Deca footprint that snaps onto DIN rail inside a control panel. The front face carries IP2X protection per VDE 0106, meaning tools and fingers are kept out of live parts. Rated for operation from -40 to 60 °C, with derating allowed up to 70 °C. Storage range is -60 to 80 °C. Altitude rating is 0 to 3000 m without derating. The TH protective treatment per IEC 60068 handles humid, tropical environments. Mechanical robustness is specified for shock and vibration: the relay stays open at 10 Gn for 11 ms (closed at 15 Gn), and withstands vibration at 2 Gn open / 4 Gn closed across 5 to 300 Hz per IEC 60068-2-27 and IEC 60068-2-6. This matters for installations on conveyors, pumps, or mobile equipment.