Skip to main content
Schneider Electric CNXAE34250

Schneider Electric CNXAE34250

MPNCNXAE34250
Obsolete

I-Line circuit breaker, 3 Poles, 250A rating, 36kA, TMD trip unit adapted ComPact NSX

$1,063.68Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

CNXAE34250 key specifications
ParameterValue
Control typeToggle
Protection typeL : for overload protection (long time) I : for short-circuit protection (magnetic)
Range of productComPact NSX100...250
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage800 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to EN/IEC 60947-2
Current250 A at 40 °C
[Ics] rated service short-circuit breaking capacity36 kA at 415 V AC 50/60 Hz conforming to EN/IEC 60947-2

All specifications

CNXAE34250 additional specifications
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity36 kA Icu at 415 V AC 50/60 Hz conforming to EN 60947-2
Poles3P
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting locationI-Line
Pollution degree3 conforming to IEC 60664-1
Relative humidity95 %
Operating altitude0...2000 m without derating 2000 m...5000 m without derating
ColorGrey
Depth86 mm
Width105 mm
Height161 mm
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability20000 cycles
StandardsEN/IEC 60947-1 EN/IEC 60947-2
RangeI-Line
Trip unit nameTM-D
Device short nameNSX250F
Safety categoryF
Device applicationDistribution
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range120...400 s at 1.5 x Ir 15 s at 6 x Ir
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Ii] instantaneous protection pick-up adjustment range5...10 x In
MPN
CNXAE34250