Schneider Electric CV1BF1F0ZM500
MPNCV1BF1F0ZM500
Obsolete
contactor TeSys CV1BF - 1 pole - AC-3 690 V 80A - coil 220 V AC
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control circuit type | AC |
| Auxiliary contacts type | type instantaneous without |
| Product or component type | Contactor |
| Coil voltage | 220 V AC 50 Hz |
| Voltage | 690 V conforming to IEC 60947-4 |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc at 50 Hz (at Drop-out: 0.5...0.7 Uc at 50 Hz (at <55 °C) |
| [Ue] rated operational voltage | Control circuit: 690 V AC 50 Hz |
| [Icw] rated short-time withstand current | 640 A 40 °C - 5 s for control circuit 640 A 40 °C - 10 s for control circuit 380 A 40 °C - 30 s for control circuit 320 A 40 °C - 60 s for control circuit 200 A 40 °C - 180 s for control circuit 130 A 40 °C - 600 s for control circuit |
| Breaking capacity | 900 A at 220/400 V for control circuit conforming to IEC 60947-4-1 800 A at 415/440 V for control circuit conforming to IEC 60947-4-1 800 A at 500 V for control circuit conforming to IEC 60947-4-1 320 A at 660/690 V for control circuit conforming to IEC 60947-4-1 |
| [Ie] rated operational current | 80 A AC for control circuit |
| Current rating code of contactor | BF |
| [Ith] conventional free air thermal current | 80 A (at 40 °C) for control circuit |
All specifications
| Parameter | Value |
|---|---|
| Inrush power in | 270 VA 50 Hz 1P (at 20 °C) |
| Power dissipation per pole | 7.6 W AC-3 9.6 W AC-1 |
| Rated operational power in | 900 VA at 48 V - electrical durability: 1000000 cycles - for control circuit 800 VA at 48 V - electrical durability: 3000000 cycles - for control circuit 450 VA at 48 V - electrical durability: 10000000 cycles - for control circuit |
| Hold-in power consumption in | 270 VA 50 Hz (at 20 °C) |
| Poles description | 1P |
| Pole contact composition | 1 NO |
| Utilisation category | AC-3 AC-1 |
| IP degree of protection | IP00 conforming to IEC 60529 |
| Connections - terminals | Control circuit: cable with lug 1 x 25 mm² Control circuit: cable connector 2 x 16 mm² Power circuit: bolted connection |
| Shock resistance | 4 gn 2 gn |
| Operating altitude | 2000 m |
| Vibration resistance | 4 gn 2 gn |
| Mechanical durability | 5000000 cycles |
| Standards | EN 60947-4 IEC 60947-4 |
| Range | TeSys |
| Operating time | 40 ms contactor closed AC 15 ms contactor open AC |
| Heat dissipation | 16 W at 50 Hz 1P for control circuit |
| Average impedance | 1.5 mOhm - Ith 80 A 50 Hz for control circuit |
| Device short name | CV1BF |
| Tightening torque | Control circuit: 1.2 N.m - on with cable end - cable 2...4 mm² Control circuit: 1.2 N.m - on with cable end - cable 1...4 mm² Power circuit: 9 N.m - on cable with lug - cable 25 mm² Power circuit: 9 N.m - on cable connector - cable 16 mm² |
| Protective treatment | TC |
| Contactor application | Resistive circuits, heating, lighting Motor |
| Associated fuse rating | 80 A aM at 125 A g1 at <= 400 V for control circuit |
| Maximum operating rate | 120 cyc/mn 55 °C |
| Irms rated making capacity | 1000 A at 690 V AC for control circuit conforming to IEC 60947-4-1 |
| Auxiliary contact composition | Without |
| Ambient air temperature for storage | -60...80 °C |
| Ambient air temperature for operation | -5...55 °C |
MPN