Skip to main content
Schneider Electric CV1BJ2J0ZMD22 — Contactors

Schneider TeSys CV1BJ2J0ZMD22 Contactor, 470A AC-3, 220VDC C

MPNCV1BJ2J0ZMD22
Active

Schneider Electric TeSys B contactor, CV1BJ2J0ZMD22, 2-pole, 470 A AC-3 at 690 V, 220 V DC coil, IP00.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

CV1BJ2J0ZMD22 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive circuits, heating, lighting Motor

Ratings & Performance

CV1BJ2J0ZMD22 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)690 V AC
Utilisation categoryAC-3 AC-1

Contacts & Poles

CV1BJ2J0ZMD22 — Contacts & Poles
ParameterValue
Pole configuration2P

Environmental

CV1BJ2J0ZMD22 — Environmental
ParameterValue
IP degree of protectionIP00IEC 60529
Operating altitude6561.68 ft (2000 m)

Approvals

CV1BJ2J0ZMD22 — Approvals
ParameterValue
StandardsEN 60947-4 IEC 60947-4

Product details

The Schneider Electric TeSys B CV1BJ2J0ZMD22 is a 2-pole power contactor rated for 470 A in AC-3 duty at 690 V AC, with a 220 V DC control coil. The AC-1 rating covers resistive loads like heating elements, where the current is lower-stress on the contacts. The 220 V DC coil has an operational range of 0.85 to 1.1 Uc (187 to 242 V DC) and drops out between 0.1 and 0.65 Uc (22 to 143 V DC) at 55 °C. That dropout margin is generous — it stays pulled in through a significant dip, but drops reliably when the control signal is removed. The coil is DC, so verify polarity and free-wheel diode placement if you're wiring it into an existing AC-coil panel.

Rated insulation voltage (Ui) is 690 V, matching the operational voltage — no derating needed for standard 400/480 V systems, and it handles 690 V line-to-line without issue. The 2-pole configuration with 2 NO main poles is typical for single-phase or DC switching, or for three-phase motor circuits where a third pole is handled externally. The auxiliary contact block is built in: 2 NO + 2 NC instantaneous contacts, which covers feedback and interlocking without an add-on block. That's a fast cycling rate — suitable for applications like conveyor indexing or press feeders where the contactor opens and closes frequently. The vibration resistance of 4 gn (2 gn in some axes) and shock resistance of 4 gn / 2 gn mean it holds up on machinery that sees moderate mechanical shock, but it's not rated for extreme impact environments. Maximum operating altitude is 2000 m without derating.

The contactor is certified to EN 60947-4 and IEC 60947-4, which covers the full scope of low-voltage switchgear and controlgear for motor starting and switching. These standards define the AC-1 and AC-3 ratings, the insulation voltage, and the operational performance. The part is classified under Schneider's 18402-WORLD SERVICE PARTS (CONTROL ACCESS) category, which is their internal service-parts coding for control components.

Frequently asked questions

What are the key ratings I need to check for fit?

The headline rating is 470 A in AC-3 (motor switching) at 690 V AC. The coil is 220 V DC with a dropout range of 0.1 to 0.65 Uc. It's a 2-pole contactor with 2 NO main poles and built-in 2 NO + 2 NC auxiliary contacts. Insulation voltage is 690 V, and it's rated for 5 million mechanical cycles.

What standards does this contactor comply with?

It's certified to EN 60947-4 and IEC 60947-4, the governing standards for contactors and motor-starters. The AC-1 and AC-3 utilisation categories are defined under these standards.

What is the TeSys range and where does this part fit?

The CV1BJ2J0ZMD22 belongs to the TeSys B range, which is Schneider's family of contactors for motor control and resistive load switching. The 'BJ' current rating code corresponds to the 470 A AC-3 rating, placing it in the higher-current segment of the TeSys B line.

MPN