Skip to main content
Schneider Electric CV1BK2K0ZM522 — Contactors

TeSys CV1BK2K0ZM522 Contactor, 2P, 630A AC-3, 220V AC Coil

MPNCV1BK2K0ZM522
Active

TeSys B, CV1BK, contactor, 2 poles, AC-3 690 V 630 A, coil 220 V AC 50 Hz, 2 NO + 2 NC auxiliary contacts.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

CV1BK2K0ZM522 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor Resistive circuits, heating, lighting

Ratings & Performance

CV1BK2K0ZM522 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)690 V AC
Utilisation categoryAC-3 AC-1

Contacts & Poles

CV1BK2K0ZM522 — Contacts & Poles
ParameterValue
Pole configuration2P

Other specifications

CV1BK2K0ZM522 — Other specifications
ParameterValue
Device short nameCV1BK
Control circuit typeAC
Pole contact composition2 NO
Coil voltage220 V AC 50 Hz
Auxiliary contact composition2 NO + 2 NC
[Ie] rated operational current630 A AC for power circuit
Current rating code of contactorBK

Product details

The TeSys B CV1BK2K0ZM522 is a 2-pole contactor rated for 630 A in AC-3 duty at 690 V AC, meaning it handles motor switching up to that current level — the AC-3 category covers starting and stopping squirrel-cage motors under full load. The same power circuit also carries an AC-1 rating for resistive loads like heating and lighting, where the current is non-inductive. The control coil is 220 V AC at 50 Hz, a standard mains-voltage coil for direct panel wiring without a separate control transformer. The contactor is built with 2 normally-open main poles and carries a factory-fitted auxiliary contact block with 2 NO + 2 NC contacts, giving you feedback or interlocking capability without an add-on module. It belongs to the TeSys B range, which is the global heavy-duty contactor family from Schneider Electric.

Frequently asked questions

What is the utilisation category and what loads does it suit?

It is rated AC-3 and AC-1. AC-3 covers motor starting and stopping under load; AC-1 covers resistive loads such as heating and lighting circuits.

What is the control coil voltage and frequency?

The coil is 220 V AC at 50 Hz, a standard mains-voltage control circuit for direct connection without a step-down transformer.

What auxiliary contacts are included?

It comes with 2 normally-open and 2 normally-closed auxiliary contacts factory-fitted, providing feedback and interlocking without an add-on block.

MPN
CV1BK2K0ZM522