Schneider Electric ENW24159

Schneider Electric ENW24159

MPNENW24159
Active

Circuit breaker frame, adapt EasyPact NW, 4 Poles, 1250A, H, fixed

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

ENW24159 key specifications
ParameterValue
Control typePush-button
Network typeAC
Range of productEasyPact NW
Product or component typeCircuit breaker
Voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage12 kV conforming to IEC 60947-2
[Icw] rated short-time withstand current65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Current1250 A at 40 °C
Breaking capacity codeH
[Ics] rated service breaking capacity65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2

All specifications

ENW24159 additional specifications
ParameterValue
[Icm] rated short-circuit making capacity143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
Protected poles description4P 4d
Utilisation categoryCategory B
IP degree of protectionIP40
Mounting modeFixed
Mounting supportBase plate
Connection pitch115 mm without spreader
Connection positionHorizontal Vertical
Location of connectionRear
Maximum closing response time70 ms
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
Electrical durabilityCategory B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Mechanical durability20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
StandardsIEC 60947-2
RangeEasyPact
Neutral positionLeft
Device short nameENW12H
Device applicationDistribution
Maximum breaking time25 ms
Circuit breaker CT rating1250 A
Suitability for isolationYes conforming to IEC 60947-2
Contact position indicatorYes
Neutral protection settingWithout protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D)
Ambient air temperature for storage-40...85 °C without control unit -25...85 °C with control unit
Ambient air temperature for operation-5...60 °C