Specifications

EX150T6HCT key specifications
ParameterValue
Type of coolingNatural convection
Range of productSquare D
Transformer typeEnergy efficient
Product or component typeTransformer
Primary voltage480 V delta
Secondary voltage240 V delta Centre tap 120 V
Let through current8.6 kA
Rated operational power in150 kVA
Network frequency60 Hz
Phases3 phase
IP ratingUL type 1 UL type 2, with 7400DS22K UL type 3R, with 7400WS22K
Mounting supportFloor Floor, with 7400FMB Ceiling, with 7400CMB22K

All specifications

EX150T6HCT additional specifications
ParameterValue
Electrical connection4 Hole Nema Pad primary 0.4 in (11.1 mm) 4 Hole Nema Pad secondary 0.4 in (11.1 mm)
Depth28.5 in (723 mm)
Width33.7 in (855 mm)
Height49.09 in (1247 mm)
Coil materialAluminium
StandardsUL 1561 CSA C22.2 No 47 NEMA ST-20
%IX0.0364 %
%IZ0.042 %
CategoryUS1PE2X16250
X (R ratio)1.71
Box number22K
Sound level47 dB 3 dB NEMA ST-20
DOE efficiency99 % at 35 % load factor , 167 °F (75.0 °C)
Temperature rise150 °C 220 °C insulated
Device short nameDOE 2016
Device applicationLow voltage electrical distribution
Number of tap-offs2 2.5 % FCAN 4 2.5 % FCBN
Transformer BTU (HR)1017.2417218764961 16.6 % 1398.5517022499998 25 % 3444.5573489999997 50 % 6854.56676025 75 % 11628.579936 100 %
Transformer losses210.0 no load (core loss) 3198.0 load loss (coil loss)
Basic IMP level10 kV
Ambient air temperature for operation104 °F (40 °C)
Average ambient air temperature for operation30 °C
MPN