Skip to main content
Schneider Electric EZ9F16106

Schneider EZ9F16106 Miniature Circuit Breaker

MPNEZ9F16106
Active

EZ9F16106 - MINIATURE by SCHNEIDER ELECTRIC

$2.90Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9F16106 key specifications
ParameterValue
Control typeToggle
Network typeAC
Product or component typeMiniature circuit-breaker
Voltage500 V AC 50/60 Hz conforming to BS EN 60898-1
[Ue] rated operational voltage230 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV conforming to BS EN 60898-1
Breaking capacity6000 A Icn at 230 V AC 50/60 Hz phase to neutral conforming to BS EN 60898-1 6000 A Icn at 400 V AC 50/60 Hz phase to phase conforming to BS EN 60898-1
Current6 A
[Ics] rated service breaking capacity6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to BS EN 60898-1
Network frequency50/60 Hz
Poles1P
Number of protected poles1

All specifications

EZ9F16106 additional specifications
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Mounting modeClip-on
Mounting supportDIN rail
Connections - terminalsTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Pollution degree2
Relative humidity95 % at 55 °C
Depth72 mm
Width18 mm
ColorGrey (RAL 7035)
Height82 mm
Electrical durability4000 cycles
Mechanical durability10000 cycles
StandardsBS EN 60898-1
RangeEasy9
Curve codeB
9 mm pitches2
Tropicalisation2
Limitation class3 conforming to BS EN 60898-1
Local signallingWithout
Device short nameEasy9 MCB
Tightening torque2 N.m top or bottom
Device applicationDistribution
Trip unit technologyThermal-magnetic
Magnetic tripping limit3...5 x In
Earth-leakage protectionWithout
Suitability for isolationYes conforming to BS EN 60898-1
Contact position indicatorYes
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-5...60 °C
MPN
EZ9F16106