Skip to main content
Schneider Electric EZC125H3125 — Molded Case Circuit Breakers (MCCB)

Schneider Electric EZC125H3125 EasyPact MCCB, 125 A, 3P, 10-

MPNEZC125H3125
Active

Schneider Electric EasyPact EZC125H3125, 125 A, 3-pole molded case circuit breaker, thermal-magnetic TM-D trip unit, 10-100 kA Icu, 60 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZC125H3125 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZC125H3125 — Mechanical
ParameterValue
Height130 mm
Width75 mm
Depth60 mm
EZC125H3125 — Electrical
ParameterValue
[In] rated current125 A at 40 °C
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity15 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 50 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
EZC125H3125 — Specifications
ParameterValue
Poles description3P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
StandardsGB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-1 EN/IEC 60947-2

Product details

It is a Category A device (no intentional short-time delay), intended for distribution applications where fast fault clearing is the priority.

The H breaking capacity code on this breaker means it delivers 100 kA Icu at 220–240 V AC and 30 kA at 400–415 V AC — figures that cover the most common panel voltages in commercial and light industrial distribution. At 440 V AC it drops to 20 kA, and at 550 V AC to 10 kA. On the DC side, it offers 10 kA Icu at 125 V DC (1-pole) and 250 V DC (2-pole).

The EZC125H3125 is certified to EN/IEC 60947-1 and EN/IEC 60947-2, with additional compliance to GB/T 14048.2 and JIS C8201-2-2. The IP20 finger-safe enclosure and IK07 impact resistance are standard for panel-mounted distribution breakers.

Fixed-mount backplate installation, 75 mm wide × 130 mm high × 60 mm deep. Front-connected line and load sides. Toggle actuator with positive contact indication — the handle position shows welded contacts, not just spring state. Connection pitch is 25 mm.

Frequently asked questions

What is the breaking capacity of the EZC125H3125 at 400 V?

30 kA Icu at 400–415 V AC, with an Ics of 7.5 kA at 400–415 V AC.

What standards does this MCCB comply with?

It is certified to EN/IEC 60947-1, EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2.

What is the operating temperature range for the EZC125H3125?

The ambient air temperature for operation is -25 to 70 °C; storage range is -35 to 85 °C.

What is the depth of the EZC125H3125?

The depth is 60 mm.

Where can I buy the EZC125H3125?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN