Skip to main content
Schneider Electric EZC250F3250 — Circuit Breaker Accessories

Schneider Electric EZC250F3250 EasyPact EZC250F, 250A, 3P, T

MPNEZC250F3250
Active

Schneider Electric EasyPact EZC250F, EZC250F3250, molded case circuit breaker, 250 A, 3-pole, thermal-magnetic TM-D trip unit, 10 kA at 440 V AC, fixed mount, front connection.

$123.13Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC250F3250 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250F3250 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]250 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZC250F3250 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]9 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeF
Trip unit technologyThermal-magnetic
Trip unit rating250 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250F3250 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250F
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width105 mm
Height165 mm
Depth60 mm
EZC250F3250 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250F3250 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1

Product details

The EZC250F3250 is a 3-pole molded case circuit breaker from Schneider Electric's EasyPact range, rated 250 A at 40 °C and 250 A at 50 °C. The 10 kA Icu at 440 V AC is the interrupting capacity at a common industrial voltage; at 400–415 V AC it rises to 15 kA, and at 380 V AC to 18 kA. For a distribution panel feeding motor control centers or lighting, that's enough fault-clearing for most 400 V class installations without cascading upstream. Rated operational voltage goes up to 550 V AC and 250 V DC.

Fixed mounting on a backplate, front connections both top and bottom. Connection pitch of 35 mm matches common busbar and lug spacing. IP20 finger-safe protection on the front, IK07 impact resistance per IEC 62262, so it handles incidental tool drops in the enclosure.

Protection and duty

The TM-D trip unit provides overload protection (thermal bimetal) and short-circuit protection (magnetic solenoid). No earth-leakage or neutral protection built in — it's a straight 3-pole breaker with all three poles protected. Category A utilization means it's not intended for frequent switching under load; it's a distribution breaker, not a motor-starter disconnect. Mechanical durability of 10,000 cycles is typical for this class — fine for infrequent switching, not for daily load-break duty.

Frequently asked questions

What are the key ratings for EZC250F3250?

Rated 250 A continuous at 40 °C, 3-pole, thermal-magnetic TM-D trip unit. Breaking capacity is 10 kA Icu at 440 V AC, 15 kA at 400–415 V AC, and 25 kA at 220–240 V AC. Operational voltage up to 550 V AC and 250 V DC.

What standards does EZC250F3250 comply with?

It complies with EN/IEC 60947-2, GB/T 14048.2, and EN/IEC 60947-1. It is suitable for isolation per IEC 60947-2 and rated for pollution degree 3.

Where can I buy EZC250F3250?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
EZC250F3250