Skip to main content
Schneider Electric EZC250H4125 — Molded Case Circuit Breakers (MCCB)

Schneider Electric EasyPact EZC250H4125 MCCB, 125 A, 85 kA a

MPNEZC250H4125
Active

Schneider Electric EasyPact EZC250H, MCCB, 125 A, 4P, thermal-magnetic TM-D trip unit, 85 kA Icu at 240 V AC, IP20, IEC 60947-2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZC250H4125 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZC250H4125 — Mechanical
ParameterValue
Height165 mm
Width140 mm
Depth60 mm
EZC250H4125 — Electrical
ParameterValue
[In] rated current125 A at 40 °C
Breaking capacity10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
EZC250H4125 — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZC250H
StandardsEN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2

Product details

It belongs to the EasyPact EZC250H family, built for distribution applications and designed for fixed backplate mounting with front-front connections.

The breaking capacity varies with system voltage: 85 kA Icu at 220–240 V AC, 36 kA at 380–415 V AC, 25 kA at 440 V AC, and 10 kA at 550 V AC. On DC sides, it delivers 30 kA Icu at 125 V DC (1P) and 30 kA at 250 V DC (2P). That spread means the same breaker can serve both 240 V high-fault panels and 400 V distribution without a frame-size change — useful when the BOM covers multiple voltage classes.

Designed and tested to EN/IEC 60947-1 and -2, JIS C8201-2-2, and GB/T 14048.2. Pollution degree 3 per IEC 60947, IP20 finger-safe enclosure, and IK07 impact resistance.

Frequently asked questions

Where can I buy EZC250H4125?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings for EZC250H4125?

Rated current 125 A at 40 °C, thermal-magnetic TM-D trip unit, breaking capacity 85 kA Icu at 240 V AC, rated insulation voltage 690 V AC, and operational voltage up to 550 V AC / 250 V DC.

What compliance documentation does Schneider provide for EZC250H4125?

The breaker is certified to EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It carries IP20 and IK07 protection ratings. RoHS and REACH declarations are typically available from Schneider's documentation portal; the evidence does not list specific material compliance statements.

MPN
EZC250H4125