Skip to main content
Schneider Electric EZC250H4150 — Circuit Breaker Accessories

Schneider EasyPact EZC250H4150 MCCB, 150 A, 4P, TM-D, 85 kA

MPNEZC250H4150
Obsolete

Schneider Electric EasyPact EZC250H series, EZC250H4150, 4-pole MCCB, 150 A rated current, thermal-magnetic TM-D trip unit, breaking capacity code H (85 kA at 240 V AC).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC250H4150 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250H4150 — Electrical
ParameterValue
Network type (AC/DC)DC AC
Rated current [In]150 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC250H4150 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating150 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250H4150 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height165 mm
Depth60 mm
EZC250H4150 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250H4150 — Approvals
ParameterValue
StandardsJIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1

Product details

The EZC250H4150 is a 4-pole molded-case circuit breaker from the Schneider EasyPact EZC250H series, rated 150 A at 40 °C and carrying a TM-D thermal-magnetic trip unit. The trip unit rating of 150 A at 50 °C means the breaker holds full rated current up to that ambient — above that, you need to consult the thermal derating curve. Breaking capacity varies by voltage: 85 kA Icu at 220–240 V AC, 36 kA at 380–415 V AC, 25 kA at 440 V AC, and 10 kA at 550 V AC. For DC applications, it delivers 30 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole). The 'H' breaking capacity code positions it for high-fault installations where upstream coordination demands a robust interrupt rating.

This breaker mounts fixed to a backplate — no DIN-rail clip, so plan for drilled mounting holes or a sub-panel. The 140 mm width and 165 mm height with 60 mm depth fit a standard distribution board footprint; the 35 mm connection pitch matches common busbar and lug spacing. Front connections both top and bottom simplify busbar runs and cable entry. IK07 impact rating handles incidental tool drops during maintenance.

Frequently asked questions

How do I get pricing and availability for EZC250H4150?

Submit an RFQ through the storefront. This part is sourced to order against a quote; current pricing and stock levels are confirmed at the time of quotation.

What is the breaking capacity of this breaker at 240 V AC?

The EZC250H4150 delivers 85 kA Icu at 220–240 V AC 50/60 Hz per IEC 60947-2. That is the highest interrupt rating on this breaker — suitable for high-fault service-entrance or sub-distribution boards.

What compliance documentation does Schneider provide for the EZC250H4150?

The breaker is certified to JIS C8201-2-2, EN/IEC 60947-2, and GB/T 14048.2. It carries IEC 60947-1 for general rules and is suitable for isolation per IEC 60947-2. RoHS and REACH declarations are standard from Schneider for the EasyPact range.

MPN