Skip to main content
Schneider Electric EZC250H4150 — Molded Case Circuit Breakers (MCCB)

Schneider EasyPact EZC250H4150 MCCB, 150 A, 4P, TM-D, 85 kA

MPNEZC250H4150
Obsolete

Schneider Electric EasyPact EZC250H series, EZC250H4150, 4-pole MCCB, 150 A rated current, thermal-magnetic TM-D trip unit, breaking capacity code H (85 kA at 240 V AC).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZC250H4150 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZC250H4150 — Mechanical
ParameterValue
Height165 mm
Width140 mm
Depth60 mm
EZC250H4150 — Electrical
ParameterValue
[In] rated current150 A at 40 °C
Breaking capacity10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
EZC250H4150 — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZC250H
StandardsJIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1

Product details

The EZC250H4150 is a 4-pole molded-case circuit breaker from the Schneider EasyPact EZC250H series, rated 150 A at 40 °C and carrying a TM-D thermal-magnetic trip unit. The trip unit rating of 150 A at 50 °C means the breaker holds full rated current up to that ambient — above that, you need to consult the thermal derating curve. Breaking capacity varies by voltage: 85 kA Icu at 220–240 V AC, 36 kA at 380–415 V AC, 25 kA at 440 V AC, and 10 kA at 550 V AC. For DC applications, it delivers 30 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole). The 'H' breaking capacity code positions it for high-fault installations where upstream coordination demands a robust interrupt rating.

This breaker mounts fixed to a backplate — no DIN-rail clip, so plan for drilled mounting holes or a sub-panel. The 140 mm width and 165 mm height with 60 mm depth fit a standard distribution board footprint; the 35 mm connection pitch matches common busbar and lug spacing. Front connections both top and bottom simplify busbar runs and cable entry. IK07 impact rating handles incidental tool drops during maintenance.

Frequently asked questions

How do I get pricing and availability for EZC250H4150?

Submit an RFQ through the storefront. This part is sourced to order against a quote; current pricing and stock levels are confirmed at the time of quotation.

What is the breaking capacity of this breaker at 240 V AC?

The EZC250H4150 delivers 85 kA Icu at 220–240 V AC 50/60 Hz per IEC 60947-2. That is the highest interrupt rating on this breaker — suitable for high-fault service-entrance or sub-distribution boards.

What compliance documentation does Schneider provide for the EZC250H4150?

The breaker is certified to JIS C8201-2-2, EN/IEC 60947-2, and GB/T 14048.2. It carries IEC 60947-1 for general rules and is suitable for isolation per IEC 60947-2. RoHS and REACH declarations are standard from Schneider for the EasyPact range.

MPN
EZC250H4150