Schneider Electric EZC250H4225
MPNEZC250H4225
Obsolete
circuit breaker Easypact EZC250H - TMD - 225 A - 4 poles 3d
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC DC |
| Protection type | Overload protection Short-circuit protection |
| Range of product | EasyPact |
| Product or component type | Circuit breaker |
| Voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Breaking capacity | 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Current | 225 A at 40 °C |
| Breaking capacity code | H |
| [Ics] rated service breaking capacity | 5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 |
All specifications
| Parameter | Value |
|---|---|
| Network frequency | 50/60 Hz |
| Poles description | 4P |
| Protected poles description | 3t |
| Utilisation category | Category A |
| IK degree of protection | IK07 conforming to EN 50102 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Mounting mode | Fixed |
| Mounting support | Backplate |
| Connection pitch | 35 mm |
| Upside connection | Front |
| Downside connection | Front |
| Pollution degree | 3 conforming to IEC 60947 |
| Depth | 60 mm |
| Width | 140 mm |
| Height | 165 mm |
| Mechanical durability | 10000 cycles |
| Standards | EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1 JIS C8201-2-2 |
| Trip unit name | TM-D |
| Local signalling | Positive contact indication |
| Trip unit rating | 225 A at 50 °C |
| Device short name | Easypact EZC250H |
| Device application | Distribution |
| Circuit breaker name | Easypact EZC250H |
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Neutral protection setting | Without protection |
| Ambient air temperature for storage | -35...85 °C |
| Ambient air temperature for operation | -25...70 °C |
MPN
EZC250H4225