Schneider Electric EZCV250H44200 — Circuit Breaker Accessories

Schneider EasyPact EZCV250H44200 MCCB, 200 A, 100 kA, 4P

MPNEZCV250H44200
Obsolete

Schneider Electric EasyPact EZCV250H series, EZCV250H44200, 200 A molded case circuit breaker, 4 poles, TM-D thermal-magnetic trip unit, 100 kA Icu at 240 V AC, with earth-leakage protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZCV250H44200 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZCV250H44200 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]200 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZCV250H44200 — Protection & Performance
ParameterValue
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating200 A at 40 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Earth-leakage protection Overload protection
Earth-leakage protectionWith
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZCV250H44200 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZCV250H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height165 mm
Depth68 mm
EZCV250H44200 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZCV250H44200 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-1 JIS C8201-2-2 GB/T 14048.2

Product details

MCCB for distribution boards — 200 A, H-frame, earth-leakage integrated

The Schneider EasyPact EZCV250H44200 is a 4-pole molded case circuit breaker rated 200 A at 40 °C, part of the EasyPact EZCV250H family. It carries a TM-D thermal-magnetic trip unit with a 100 kA Icu breaking capacity at 220–240 V AC (50/60 Hz) per IEC 60947-2, stepping down to 36 kA at 380–415 V and 25 kA at 440 V. Earth-leakage protection is built in, so it covers both overload/short-circuit and ground-fault in one device, saving a panel row versus a separate ELCB. The toggle handle gives positive contact indication — you see the position, no ambiguity.

The 100 kA Icu at 240 V AC is the headline number, but the 25 kA Icu at 440 V AC is the one that governs most 400 V-class industrial panels. At 380–415 V it holds 36 kA — enough for most secondary distribution boards behind a 1 MVA transformer. The TM-D trip unit is thermal-magnetic, not electronic: no auxiliary power needed, no adjustment dials, just a fixed thermal curve for overload and a fixed magnetic pickup for short-circuit. That makes it a straight swap for an older thermal-magnetic MCCB without re-coordination studies. Rated insulation and operational voltage both sit at 440 V AC — match that to your system voltage. The 4 poles protect all phases; neutral protection is not provided (the neutral pole is switched but not protected). If your design requires a protected neutral, this is not the variant. Mechanical durability of 10,000 cycles is typical for a distribution breaker — not a concern for infrequent switching, but not rated for daily load-break duty.

Environmental and physical fit

Dimensions: 165 mm high, 140 mm wide, 68 mm deep. IP20 finger-safe terminals; IK07 impact resistance covers accidental tool drops during panel work. Standards compliance includes IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2, so it is accepted in European, Japanese, and Chinese installations without additional certification paperwork.

Frequently asked questions

What is the breaking capacity of the EZCV250H44200 at different voltages?

100 kA Icu at 220–240 V AC, 36 kA at 380–415 V AC, and 25 kA at 440 V AC, all per IEC 60947-2. The H code designates this high-interrupting version.

Does the EZCV250H44200 include earth-leakage protection?

Yes, earth-leakage protection is integrated into this breaker. It covers short-circuit, overload, and ground-fault in a single device.

Where can I buy the EZCV250H44200 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Current availability and pricing are confirmed at quote time — submit an RFQ for a firm response.

What compliance documentation is available for the EZCV250H44200?

The breaker is certified to IEC 60947-2, IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2. It carries IP20 and IK07 ratings. RoHS and REACH compliance documentation is typically provided by the manufacturer upon request.

MPN