Skip to main content
Schneider Electric EZCV250N3100 — Molded Case Circuit Breakers (MCCB)

Schneider Electric EZCV250N3100 EasyPact MCCB, 100 A, 20 kA

MPNEZCV250N3100
Obsolete

Schneider Electric EasyPact EZCV250N series, EZCV250N3100, 3-pole MCCB, 100 A thermal-magnetic TM-D trip unit, 20 kA Icu at 440 V AC, with integrated earth-leakage protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZCV250N3100 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZCV250N3100 — Mechanical
ParameterValue
Height165 mm
Width105 mm
Depth68 mm
EZCV250N3100 — Electrical
ParameterValue
[In] rated current100 A at 40 °C
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage440 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to IEC 60947-2
EZCV250N3100 — Specifications
ParameterValue
Poles description3P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZCV250N
StandardsGB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-2 EN/IEC 60947-1

Product details

What this MCCB brings to an existing panel

It breaks 20 kA Icu at 440 V AC (85 kA at 240 V AC) per IEC 60947-2, and carries integrated earth-leakage protection — so it covers both overcurrent and ground-fault in one device, no separate RCCB needed downstream.

At 380–415 V it delivers 25 kA Icu, and at 220–240 V it hits 85 kA Icu, so it coordinates cleanly with a downstream 10 kA MCB without the main breaker opening first. The Category A utilisation rating tells you it is not intended for motor starting duty under IEC 60947-2; this is a line-side or feeder breaker, not a motor-circuit protector.

Current production — no lifecycle concern

It is a standard catalogue item in the EasyPact range, compliant with IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2.

Fixed backplate mounting, front-front connections (both line and load side), with a 35 mm connection pitch. The toggle control and positive contact indication give a visual break confirmation — useful for lockout/tagout. IP20 finger-safe terminals and IK07 impact rating mean it handles the usual panel environment without a separate enclosure.

Frequently asked questions

Where can I buy EZCV250N3100?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest alternative to EZCV250N3100 in the EasyPact family?

Within the same EZCV250N frame, the key variant is the thermal-magnetic only version (without earth-leakage) — same 100 A TM-D trip, same 20 kA Icu, but omits the integrated Vigi module. If you need the earth-leakage function, stick with the 3100 suffix; if you don't, the non-Vigi variant saves panel space and cost.

What compliance documentation does Schneider provide for EZCV250N3100?

The breaker is certified to IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2. It carries IP20 and IK07 ratings. Standard Schneider documentation includes the IEC declaration of conformity and the product datasheet; RoHS and REACH compliance statements are available on request.

MPN
EZCV250N3100