What this MCCB brings to an existing panel
It breaks 20 kA Icu at 440 V AC (85 kA at 240 V AC) per IEC 60947-2, and carries integrated earth-leakage protection — so it covers both overcurrent and ground-fault in one device, no separate RCCB needed downstream.
At 380–415 V it delivers 25 kA Icu, and at 220–240 V it hits 85 kA Icu, so it coordinates cleanly with a downstream 10 kA MCB without the main breaker opening first. The Category A utilisation rating tells you it is not intended for motor starting duty under IEC 60947-2; this is a line-side or feeder breaker, not a motor-circuit protector.
Current production — no lifecycle concern
It is a standard catalogue item in the EasyPact range, compliant with IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2.
Fixed backplate mounting, front-front connections (both line and load side), with a 35 mm connection pitch. The toggle control and positive contact indication give a visual break confirmation — useful for lockout/tagout. IP20 finger-safe terminals and IK07 impact rating mean it handles the usual panel environment without a separate enclosure.