Skip to main content
Schneider Electric EZCV250N3250 — Molded Case Circuit Breakers (MCCB)

Schneider Electric EZCV250N3250 EasyPact EZCV250N, 250A 3P M

MPNEZCV250N3250
Obsolete

Schneider Electric EasyPact EZCV250N, 3-pole MCCB, 250 A at 40 °C, TM-D thermal-magnetic trip, 20 kA Icu at 440 V AC, with earth-leakage protection, IP20, backplate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZCV250N3250 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
EZCV250N3250 — Mechanical
ParameterValue
Height165 mm
Width105 mm
Depth68 mm
EZCV250N3250 — Electrical
ParameterValue
[In] rated current250 A at 40 °C
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage440 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to IEC 60947-2
EZCV250N3250 — Specifications
ParameterValue
Poles description3P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameEasypact EZCV250N
StandardsJIS C8201-2-2 EN/IEC 60947-1 EN/IEC 60947-2 GB/T 14048.2

Product details

The Schneider Electric EZCV250N3250 is a 3-pole moulded-case circuit breaker from the EasyPact EZCV250N range, rated 250 A at 40 °C and built for distribution duty in commercial and industrial panels. The 20 kA Icu at 440 V AC (IEC 60947-2) is the interrupting rating that governs its fault-clearing capability on a 400 V line; the 85 kA Icu at 240 V AC is higher but only relevant for lower-voltage taps. For a 380–415 V supply the rating is 25 kA Icu, which is the more common figure for European 400 V distribution boards.

The TM-D trip unit is a fixed thermal-magnetic design — the thermal element responds to sustained overloads, the magnetic element to short-circuit peaks. Category A utilisation means it is not intended for motor starting under frequent switching; it is a distribution breaker for feeder and branch circuits. The 10,000-cycle mechanical durability is typical for a panel-mounted MCCB that sees occasional switching, not daily operation. Pollution degree 3 (IEC 60947) means it is rated for conductive pollution in an industrial enclosure — standard for a backplate-mounted breaker in a non-sealed panel.

Mounts fixed to a backplate — no DIN-rail adapter. Front connections on both line and load sides, with a 35 mm connection pitch that matches standard busbar systems. Dimensions are 105 mm wide by 165 mm high by 68 mm deep, so it occupies a 3-pole MCCB footprint typical for 250 A frames. The toggle control and positive contact indication give a visual open/closed status without needing auxiliary contacts.

Frequently asked questions

How do I get current pricing and availability for EZCV250N3250?

Submit an RFQ through this listing. The part is sourced through independent distribution and quoted to order; availability and current pricing are confirmed at quote time.

What is the breaking capacity of EZCV250N3250 at 440 V?

The breaking capacity is 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2. At 380–415 V it is 25 kA Icu, and at 220–240 V it is 85 kA Icu.

What compliance documentation does this breaker carry?

It is certified to IEC 60947-2, EN 60947-2, GB/T 14048.2, and JIS C8201-2-2. It is suitable for isolation per IEC 60947-2 and carries IP20 and IK07 protection ratings.

MPN
EZCV250N3250