Schneider Electric G12E3F20 — Miniature Circuit Breakers (MCB)

Schneider Electric G12E3F20 GoPact MCCB 125, 20 A, 15 kA, 3P

MPNG12E3F20
Active

Schneider Electric GoPact MCCB 125, thermal-magnetic circuit breaker, 20 A at 40 °C, 15 kA at 415 V AC, 3 poles, TM-D trip unit, IP20, grey (RAL 7035).

$81.29Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12E3F20 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12E3F20 — Ratings
ParameterValue
Rated current (In)20 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12E3F20 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12E3F20 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12E3F20 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12E3F20 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12E3F20 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12E3F20 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

Distribution-grade MCCB with thermal-magnetic trip

The Schneider Electric G12E3F20 is a GoPact MCCB 125 thermal-magnetic circuit breaker rated 20 A at 40 °C, with a breaking capacity of 15 kA at 380/415 V AC (performance level E). It is a 3-pole, fixed-mount device with a TM-D trip unit providing LI protection — thermal for overload (L) and magnetic for short-circuit (I). Rated operational voltage is 415 V AC at 50/60 Hz, with an insulation voltage of 440 V AC, both conforming to EN/IEC 60947-2. The utilisation category is A (no intentional short-time delay), making it suitable for distribution feeder protection rather than motor-starting duty.

Above 40 °C, derate per the IEC 60947-2 thermal curve — the spec gives the number at 40 °C, so a 50 °C panel environment reduces that figure. Power dissipation is 18.7 W per pole, so total 56.1 W at rated load. This heat must be considered in enclosure sizing, especially in a multi-breaker panel. The IP20 finger-safe terminals (screw-type, front-connected) are suitable for enclosed distribution boards but not for washdown environments.

Fixed-mount via backplate, accepting horizontal or vertical orientation. Connection pitch is 25 mm, screw terminals front-connected on both line and load sides. Pollution degree 3 (conductive pollution, typical of industrial panels) and overvoltage category III (distribution level) confirm it is designed for fixed-installation switchgear.

Compliance and approvals

Suitability for isolation is confirmed per EN/IEC 60947-2, meaning it provides visible isolation when in the OFF position. Ambient operating range is -20 to 55 °C; storage range -35 to 85 °C. Mechanical durability is 30,000 cycles, electrical durability 8,000 cycles at rated current and voltage.

Frequently asked questions

Where can I buy G12E3F20 and how is it quoted?

The G12E3F20 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of G12E3F20?

The breaking capacity is 15 kA at 380/415 V AC (performance level E). This is the maximum fault current it can safely interrupt at that voltage.

What standards does G12E3F20 comply with?

It conforms to EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H. It is also certified for isolation per EN/IEC 60947-2.

What is the colour and size of G12E3F20?

Colour is grey (RAL 7035). Dimensions: 130 mm height, 75 mm width, 60 mm depth.

MPN
G12E3F20