Skip to main content
Schneider Electric G12E3F25 — Miniature Circuit Breakers (MCB)

Schneider Electric G12E3F25 GoPact MCCB 125, 25 A, 15 kA, 3P

MPNG12E3F25
Active

Schneider Electric GoPact MCCB 125, 25 A, 15 kA 380/415 V AC, 3P, TM-D thermal-magnetic trip unit, screw terminals, IP20, grey RAL 7035.

$81.53Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12E3F25 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12E3F25 — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12E3F25 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12E3F25 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12E3F25 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12E3F25 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12E3F25 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12E3F25 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric G12E3F25 is a GoPact MCCB 125 moulded-case circuit breaker rated 25 A at 40 °C, with a 15 kA breaking capacity at 380/415 V AC. Rated operational voltage is 415 V AC 50/60 Hz, and the insulation voltage is 440 V AC — both conforming to EN/IEC 60947-2. The utilisation category is A, meaning it is not intended for frequent switching of motor loads but for distribution protection where the breaker opens only under fault conditions.

If the ambient temperature in your panel runs higher — say 50 °C — you need to derate; the operating range is -20 to 55 °C, but the 25 A figure is only guaranteed at 40 °C. That is adequate for most secondary distribution panels fed from a transformer of 630 kVA or smaller. Power dissipation is 18.7 W per pole, so at full load the three poles together dissipate about 56 W inside the enclosure. That heat must be considered when sizing the cabinet and spacing between breakers — tight packing without ventilation can raise internal temperature and reduce the effective rating.

Deployment context and mounting

This MCCB mounts fixed to a backplate — not DIN rail — so plan for screw-down installation with a 25 mm connection pitch. Both line and load connections are front-accessed screw terminals, which simplifies wiring in a panel but means the breaker occupies a fixed footprint of 75 mm wide by 130 mm high by 60 mm deep. The IP20 degree of protection means it is finger-safe but not sealed against water or dust ingress — suitable for indoor panel installation only. If your application requires washdown or outdoor exposure, this breaker needs to be inside a sealed enclosure.

Frequently asked questions

What is the breaking capacity of G12E3F25?

The breaking capacity is 15 kA at 380/415 V AC, which is the maximum fault current the breaker can safely interrupt at that voltage.

What standards does the G12E3F25 comply with?

It conforms to EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H, and is suitable for isolation per those standards.

Where can I buy the G12E3F25 and get current pricing?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quotation — submit an RFQ for a firm price and lead time.

MPN