Skip to main content
Schneider Electric G12E3F125 — Miniature Circuit Breakers (MCB)

Schneider Electric G12E3F125 GoPact MCCB 125, 125 A, 15 kA,

MPNG12E3F125
Active

Schneider Electric GoPact MCCB 125, 125 A, 3P, thermal-magnetic TM-D trip unit, 15 kA at 415 V AC, IP20, grey (RAL 7035).

$95.65Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12E3F125 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12E3F125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12E3F125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)5000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12E3F125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12E3F125 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12E3F125 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12E3F125 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12E3F125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

IP20 finger-safe protection means it is suitable for enclosed panel installation where personnel access is restricted to qualified electricians.

Within the GoPact MCCB family, this 125 A TM-D unit is the mid-range thermal-magnetic option — higher than the 100 A frame, lower than the 160 A. The TM-D trip unit is the standard thermal-magnetic type for distribution; if you need electronic trip adjustability (LSI or LSIG), you step up to the GoPact EZC or NSX series. The deciding factor for this part is fixed 125 A protection with no adjustment — simple, reliable, and footprint-matched to the existing panel cutout.

Rated operational voltage is 415 V AC 50/60 Hz per EN/IEC 60947-2, with an insulation voltage of 440 V AC. It is suitable for isolation per the same standard — meaning when open, it provides a visible-break isolation gap for safe maintenance. Electrical durability is 5000 cycles at rated current and voltage; mechanical durability is 30,000 cycles. Ambient operating range is -20 to 55 °C; storage range is -35 to 85 °C.

Frequently asked questions

Where can I buy the G12E3F125 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is the breaking capacity of the G12E3F125?

The performance level is E, which corresponds to 15 kA at 380/415 V AC. That is the maximum fault current it can safely interrupt at that voltage.

What standards does the G12E3F125 comply with?

It complies with EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H. It is also suitable for isolation per EN/IEC 60947-2.

MPN
G12E3F125