Skip to main content
Schneider Electric G12F4A125 — Miniature Circuit Breakers (MCB)

Schneider GoPact G12F4A125 MCCB 125A 30kA 4P TM-D

MPNG12F4A125
Active

Schneider Electric GoPact MCCB 125 series, G12F4A125, 4-pole thermal-magnetic circuit breaker, 125 A rated current, 30 kA breaking capacity at 415 V AC, TM-D trip unit, IP20.

$129.13Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12F4A125 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12F4A125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12F4A125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)5000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12F4A125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12F4A125 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12F4A125 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12F4A125 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity30 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12F4A125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.8...1 x In
Trip unit protection functionsLI

Product details

125 A MCCB for distribution panels — TM-D trip, 30 kA at 415 V

The Schneider Electric GoPact G12F4A125 is a 4-pole molded case circuit breaker rated 125 A at 40 °C, with a 30 kA breaking capacity at 380/415 V AC — enough for most commercial and light industrial distribution boards where fault levels stay under that threshold. The thermal-magnetic TM-D trip unit gives you fixed LI protection: thermal overload (L) and magnetic short-circuit (I). No adjustable settings, so this is a straight swap for a BOM that already calls for a 125 A fixed-trip MCCB.

Mounts fixed to a backplate in any orientation (horizontal, vertical, flat). IP20 finger-safe terminals; the 100 x 130 x 60 mm footprint fits standard MCCB cutouts. Neutral is on the left, and the 4D protection covers all poles including neutral.

The G12F4A125 is current-production.

Frequently asked questions

What compliance documentation is available for G12F4A125?

It is certified to EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H. The IP20 rating is per IEC 60529.

MPN
G12F4A125