Skip to main content
Schneider Electric G12F4F125 — Miniature Circuit Breakers (MCB)

Schneider Electric G12F4F125 GoPact MCCB 125, 125 A, 30 kA,

MPNG12F4F125
Active

Schneider Electric GoPact MCCB 125, G12F4F125, 4P 4D, 125 A at 40 °C, F 30 kA at 415 V AC, TM-D thermal-magnetic trip unit, IP20, screw terminals, front-front connection.

$125.67Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12F4F125 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12F4F125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12F4F125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)5000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12F4F125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12F4F125 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12F4F125 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12F4F125 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity30 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12F4F125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric G12F4F125 is a GoPact MCCB 125 molded case circuit breaker rated 125 A at 40 °C, with a breaking capacity of 30 kA at 380/415 V AC (performance level F). It is a 4-pole, 4-protected-pole (4D) unit with the neutral on the left, using a TM-D thermal-magnetic trip unit providing LI protection — thermal for overload (L) and magnetic for short-circuit (I). This is a distribution-class breaker (Category A) with front-front screw terminal connections, fixed mounting on a backplate, and a 25 mm connection pitch. The enclosure is IP20 finger-safe, grey (RAL 7035), and measures 130 mm high by 100 mm wide by 60 mm deep.

The TM-D trip unit is thermal-magnetic, so overload protection follows a thermal curve (slower for small overcurrents) and short-circuit protection is magnetic (instantaneous above a set threshold). The 4D configuration protects all four poles (, L2, L3, N) with the same thermal-magnetic element — the neutral is switched and protected, not just a solid link.

Integration and mounting notes

Front-front connection (both line and load terminals on the front face) simplifies wiring in panel layouts where rear access is limited. Screw terminals accept standard copper conductors. The IP20 rating means it is finger-safe but not protected against water ingress — install inside a suitable enclosure.

Frequently asked questions

Who supplies G12F4F125 and how is it quoted for volume purchases?

The G12F4F125 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What are the key ratings of G12F4F125?

The G12F4F125 is rated 125 A at 40 °C, with a breaking capacity of 30 kA at 380/415 V AC (performance level F). It is a 4-pole, 4-protected-pole (4D) unit with a TM-D thermal-magnetic trip unit providing LI protection. Operational voltage is 415 V AC 50/60 Hz, insulation voltage is 440 V AC.

What compliance documentation does this brand provide for G12F4F125?

The G12F4F125 complies with EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H standards. It is suitable for isolation per EN/IEC 60947-2. The IP20 degree of protection conforms to IEC 60529. Pollution degree 3 conforms to IEC 60664-1.

MPN
G12F4F125