The Schneider Electric G12T4F125 is a GoPact MCCB 125 molded-case circuit breaker with a 125 A TM-D thermal-magnetic trip unit, rated for 415 V AC 50/60 Hz distribution duty. The 4-pole (4D) configuration with neutral protection set at 1 x Ir covers three-phase-plus-neutral systems where the neutral is fully rated. Screw terminals front-connected top and bottom simplify panel wiring; the 25 mm connection pitch aligns with standard busbar spacing. IP20 finger-safe protection means it's intended for enclosed panel mounting — not for exposed outdoor or washdown locations. Backplate mounting, horizontal or vertical flat, gives layout flexibility in tight enclosures.
Schneider Electric G12T4F125 GoPact MCCB 125, 125 A, 10 kA,
Schneider Electric GoPact MCCB 125, 4-pole, 125 A, thermal-magnetic TM-D trip unit, 10 kA at 415 V AC, IP20, EN/IEC 60947-2.
Specifications
| Parameter | Value |
|---|---|
| Product name | GoPact MCCB 125 |
| Product range (series) | GoPact MCCB |
| Product/component type | Circuit breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 125 A at 40 °C |
| Poles configuration | 4P |
| Rated operational voltage (Ue) | 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Rated insulation voltage (Ui) | 440 V AC conforming to EN/IEC 60947-2 |
| Rated impulse withstand voltage (Uimp) | 6 kV conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Overvoltage category | III |
| Parameter | Value |
|---|---|
| Trip unit technology | Thermal-magnetic |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Electrical durability (cycles) | 5000 cycles at 415 V In |
| Mechanical durability (cycles) | 30000 cycles |
| Parameter | Value |
|---|---|
| Mounting support | Backplate |
| Control type | Toggle |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -20...55 °C |
| Storage ambient temperature | -35...85 °C |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H |
| Parameter | Value |
|---|---|
| [Icu] rated ultimate short-circuit breaking capacity | 10 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 10 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Parameter | Value |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 1 x In |
| Trip unit protection functions | LI |
Product details
Frequently asked questions
Where can I buy G12T4F125 and how do I get a price?
The G12T4F125 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.
What are the key ratings of G12T4F125?
125 A rated current at 40 °C, 10 kA breaking capacity at 380/415 V AC (performance level T), 4-pole with TM-D thermal-magnetic trip unit, rated operational voltage 415 V AC 50/60 Hz.
What compliance documentation does this brand provide for G12T4F125?
The G12T4F125 complies with EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H for isolation suitability. It carries an IP20 protection rating per IEC 60529.