Skip to main content
Schneider Electric GC10040M5

Schneider GC10040M5 Fuse

MPNGC10040M5
Active

GC10040M5 by SCHNEIDER ELECTRIC

$261.62Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GC10040M5 key specifications
ParameterValue
Control typeRemote control
Control circuit typeAC at 50 Hz
Product or component typeModular contactor
Coil voltage220...240 V AC 50 Hz
Voltage500 V conforming to IEC 61095 500 V conforming to VDE 0110
Control circuit voltage limitsDrop-out: 0.2...0.75 Uc at 50 Hz (at Operational: 0.85...1.1 Uc at 50 Hz (at <50 °C)
[Ue] rated operational voltage<= 250 V AC
[Uimp] rated impulse withstand voltage4 kV
[Icw] rated short-time withstand current800 A 40 °C - 10 s for power circuit 250 A 40 °C - 30 s for power circuit
[Ie] rated operational current100 A AC-7A
[Ith] conventional free air thermal current100 A (at 50 °C) for power circuit
Inrush power in106 VA 50 Hz (at 20 °C)

All specifications

GC10040M5 additional specifications
ParameterValue
Power dissipation per pole10 W
Power pole contact composition4 NO
Hold-in power consumption in13 VA 50 Hz (at 20 °C)
Poles description4P
Utilisation categoryAC-7A
IP degree of protectionIP40 conforming to VDE 0106 (in enclosure) IP20 conforming to VDE 0106
Mounting modeClip-on
Mounting supportDIN rail
Connections - terminalsPower circuit: screw clamp terminals 1 cable(s) 35 mm²flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 35 mm²flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 35 mm²solid without cable end Power circuit: screw clamp terminals 2 cable(s) 10 mm²solid without cable end Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 2.5 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1.5 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²solid without cable end
Operating altitude<= 3000 m
Depth62.5 mm
Width108 mm
ColorWhite
Height85 mm
Electrical durabilityAC-7A: 30000 cycles
Mechanical durability1000000 cycles
StandardsIEC 60947-5 IEC 61095
RangeTeSys
Operating time10...25 ms opening 10...30 ms closing
Heat dissipation4.2 W at 50/60 Hz
Quantity per setSet of 2
Average impedance1 mOhm - Ith 100 A 50 Hz for power circuit
Device short nameGC100
Tightening torqueControl circuit: 0.8 N.m - on screw clamp terminals Power circuit: 3.5 N.m - on screw clamp terminals
Operating position30°/vertical
Protective treatmentTC
Contactor applicationLighting Heating Motor control
Mechanical robustnessShocks contactor open: 10 Gn for 11 ms Shocks contactor closed: 15 Gn for 11 ms Vibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 3 Gn, 5...300 Hz
Associated fuse rating100 A gL at <= 440 V for power circuit
Maximum operating rate300 cyc/h 50 °C
Total number of 18 mm modules6
Ambient air temperature for storage-40...70 °C
Ambient air temperature for operation-5...50 °C
MPN
GC10040M5