Skip to main content
Schneider Electric GC1611B5

Schneider GC1611B5 TeSys GC contactor, 2-pole, 16 A, 24 V AC

MPNGC1611B5
Obsolete

Schneider GC1611B5 Electrical Contactors — now discontinued, supplied from remaining surplus and broker stock.

$45.72Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GC1611B5 key specifications
ParameterValue
Control typeRemote control
Control circuit typeAC at 50 Hz
Product or component typeModular contactor
Coil voltage24 V AC 50 Hz
Voltage500 V conforming to IEC 61095 500 V conforming to VDE 0110
Control circuit voltage limitsDrop-out: 0.2...0.75 Uc at 50 Hz (at Operational: 0.85...1.1 Uc at 50 Hz (at <50 °C)
[Ue] rated operational voltage<= 250 V AC
[Uimp] rated impulse withstand voltage4 kV
[Icw] rated short-time withstand current128 A 40 °C - 10 s for power circuit 40 A 40 °C - 30 s for power circuit
Breaking capacity40 A at 400 V for power circuit conforming to IEC 61095
[Ie] rated operational current16 A AC-7A 5 A AC-7B
[Ith] conventional free air thermal current16 A (at 50 °C) for power circuit

All specifications

GC1611B5 additional specifications
ParameterValue
Inrush power in15 VA 50 Hz (at 20 °C)
Power dissipation per pole0.65 W
Power pole contact composition1 NO + 1 NC
Hold-in power consumption in3.8 VA 50 Hz (at 20 °C)
Poles description2P
Utilisation categoryAC-7B AC-7A
IP degree of protectionIP40 conforming to VDE 0106 (in enclosure) IP20 conforming to VDE 0106
Mounting modeClip-on
Mounting supportDIN rail
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 2.5 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1.5 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²solid without cable end Power circuit: screw clamp terminals 1 cable(s) 6 mm²flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 4 mm²flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 6 mm²flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 6 mm²solid without cable end Power circuit: screw clamp terminals 2 cable(s) 4 mm²solid without cable end
Operating altitude<= 3000 m
Depth62.5 mm
Width17.5 mm
ColorWhite
Height81 mm
Product weight0.11 kg
Electrical durabilityAC-7A: 100000 cycles AC-7B: 100000 cycles
Mechanical durability1000000 cycles
StandardsIEC 60947-5 IEC 61095
RangeTeSys
Operating time10...25 ms opening 10...30 ms closing
Heat dissipation1.3 W at 50/60 Hz
Quantity per setSet of 12
Average impedance2.5 mOhm - Ith 16 A 50 Hz for power circuit
Device short nameGC16
Tightening torqueControl circuit: 0.8 N.m - on screw clamp terminals Power circuit: 0.8 N.m - on screw clamp terminals
Operating position30°/vertical
Protective treatmentTC
Contactor applicationHeating Lighting Motor control
Mechanical robustnessShocks contactor open: 10 Gn for 11 ms Shocks contactor closed: 15 Gn for 11 ms Vibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 3 Gn, 5...300 Hz
Associated fuse rating16 A gL at <= 440 V for power circuit
Maximum operating rate300 cyc/h 50 °C
Irms rated making capacity40 A at 400 V AC for power circuit conforming to IEC 61095
Total number of 18 mm modules1
Ambient air temperature for storage-40...70 °C
Ambient air temperature for operation-5...50 °C

Product details

Overview

The GC1611B5 is a 2-pole TeSys GC contactor rated for 16 A switching current with a 40 A breaking capacity at 400 V AC, energised by a 24 V AC 50 Hz coil. It carries one normally-open and one normally-closed auxiliary contact and is built to IEC 60947-5 and IEC 61095.

Rated for AC-7A and AC-7B utilization, the GC1611B5 is sized for motor control and resistive loads such as heating and lighting, not for general power switching or high-inrush inductive loads. The 16 A switching current and 40 A breaking capacity at 400 V match it to small motors and lighting circuits within that envelope.

Compared to the 4-pole TeSys K LC1K09004F7 (9 A, 110 A making capacity at 400 V), the GC1611B5 offers a higher 16 A switching current but only 2 poles and a lower 40 A breaking capacity. The LC1K09004F7 suits multi-pole motor circuits needing higher fault making, while the GC1611B5 fits compact 2-pole heating or lighting panels where 16 A is the load limit.

MPN
GC1611B5