TeSys GF - impulse relay - 16 A - 1 NO + 1 NC - 110 V AC 50/60 Hz coil

$76.38Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GF1611F7 key specifications
ParameterValue
Control circuit typeAC at 50/60 Hz
Product or component typeImpulse relay
Coil voltage110 V AC 50/60 Hz
Voltage400 V conforming to IEC 60947-5-1 400 V conforming to VDE 0110
Control circuit voltage limits0.85...1.1 Uc 50 °C 50/60 Hz
[Ue] rated operational voltage250 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV in enclosure
[Ie] rated operational current16 A AC-1
[Ith] conventional free air thermal current16 A (at 50 °C)
Power dissipation per pole1 W
Poles description2P
Pole contact composition1 NO + 1 NC

All specifications

GF1611F7 additional specifications
ParameterValue
Utilisation categoryAC-1
IP degree of protectionIP40 conforming to VDE 0106 (in enclosure) IP20 conforming to VDE 0106
Mounting modeClip-on
Mounting support35 mm symmetrical DIN rail
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1.5 mm² solid without cable end Control circuit: screw clamp terminals 1 cable(s) 2.5 mm² flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 2.5 mm² flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm² flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm² solid without cable end Control circuit: screw clamp terminals 2 cable(s) 2.5 mm² flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 0.5...6 mm² flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 0.5...6 mm² flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 0.5...6 mm² solid without cable end Power circuit: screw clamp terminals 2 cable(s) 0.5...4 mm² flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 0.5...4 mm² flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 0.5...4 mm² solid without cable end
Operating altitude<= 2000 m without derating
Depth64 mm
Width18 mm
Height81 mm
Product weight0.11 kg
Electrical durability100000 cycles AC-22 200000 cycles AC-21
Mechanical durability1 Mcycles
StandardsIEC 60669-1 NF C 61-112 IEC 60669-2
RangeTeSys
9 mm pitches2
Operating time70 ms closing 70 ms opening
Impulse duration>= 70 ms
Quantity per setSet of 12
Average impedance4 mOhm at 50 Hz - Ith 16 A
Device short nameGF16
Tightening torqueControl circuit: 0.8 N.m - on screw clamp terminals Power circuit: 0.8 N.m - on screw clamp terminals
Operating position+/- 90° to vertical plane
Average consumption19 VA AC 50 Hz at at Uc at 20 ºC
Protective treatmentTC
Mechanical robustnessVibrations contactor open: 4 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz
Maximum operating rate900 cyc/h
Permissible short-time rating320 A 40 °C 1 s 48 A 40 °C 30 s 96 A 40 °C 10 s
Ambient air temperature for storage-40...80 °C
Ambient air temperature for operation-20...50 °C