Skip to main content
Schneider Electric GS1K4 — Contactors

TeSys GS1K4 Fuse Switch Disconnector Body, 125 A, Obsolete

MPNGS1K4
Obsolete

Schneider Electric TeSys GS series, GS1K4 fuse switch disconnector body, 4 poles, NFC fuse type, 125 A rated operational current.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GS1K4 — Identification
ParameterValue
Product / component typeFuse switch disconnector body
GS1K4 — Contacts & Poles
ParameterValue
Pole configuration4P
GS1K4 — Environmental
ParameterValue
IP degree of protectionIP20 IEC 60529 with terminal cover)
Protective treatment / pollution degreeTH
Fire resistance1562 °F (850 °C) fuse cover IEC 60695-2-1 1760 °F (960 °C) body IEC 60695-2-1
GS1K4 — Approvals
ParameterValue
StandardsIEC 60947-3 IEC 60269-2 IEC 60269-1

Product details

The Schneider Electric GS1K4 is a TeSys GS fuse switch disconnector body — a 4-pole, NFC-type unit rated for 125 A at 400 V AC-23A and 100 A at 690 V AC-23A with the terminal cover fitted. The AC-23A duty class means it is designed for occasional switching of motor loads and other highly inductive circuits, not continuous on-load making and breaking.

This body accepts 22 x 58 mm NFC fuses and mounts on a rail or plate. The power circuit terminates via bars or screw terminals accepting 35 to 95 mm² flexible cable, torqued to 12 N·m. An external right-side or frontal operating handle is required separately.

The GS1K4 is classified as obsolete by the manufacturer. If you are freezing a new design, the TeSys GS family has been superseded by the TeSys GV range; verify footprint and fuse accommodation before substituting.

The GS1K4 is designed and tested to IEC 60947-3 (switch-disconnectors), IEC 60269-2 (fuses for industrial applications), and IEC 60269-1 (general fuse requirements). The fuse cover passes the glow-wire test at 850 °C and the body at 960 °C per IEC 60695-2-1, confirming fire resistance for panel use. Insulation voltage is rated at 750 V AC, impulse withstand at 8 kV.

Frequently asked questions

What is the GS1K4's rated operational current?

The GS1K4 is rated 125 A at 400 V AC-23A and AC-23B, and 100 A at 690 V AC-23A and AC-23B with the terminal cover fitted. For DC applications, it is rated 100 A at 440 V with two poles in series per phase for both DC-23A and DC-23B duty.

What fuse size does the GS1K4 accept?

The GS1K4 accepts 22 x 58 mm NFC-type fuses.

What standards does the GS1K4 comply with?

The GS1K4 complies with IEC 60947-3 (switch-disconnectors), IEC 60269-2 (industrial fuse applications), and IEC 60269-1 (general fuse requirements). The enclosure materials pass glow-wire testing at 850 °C (cover) and 960 °C (body) per IEC 60695-2-1.

How do I source the obsolete GS1K4?

Since the GS1K4 is obsolete, it is sourced through the surplus and broker channel. Submit an RFQ for a quote — no stock or lead time is carried on this code.

MPN