GS1LG4 TeSys GS Fuse Switch Disconnector Body, 160 A, 4P

MPNGS1LG4
Obsolete

Schneider Electric TeSys GS, fuse switch disconnector body, 4 poles, DIN rail mount, 160 A rated operational current.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GS1LG4 — Identification
ParameterValue
Product / component typeFuse switch disconnector body
GS1LG4 — Contacts & Poles
ParameterValue
Pole configuration4P
GS1LG4 — Environmental
ParameterValue
IP degree of protectionIP20 IEC 60529 with terminal cover)
Protective treatment / pollution degreeTH
Fire resistance1562 °F (850 °C) fuse cover IEC 60695-2-1 1760 °F (960 °C) body IEC 60695-2-1
GS1LG4 — Approvals
ParameterValue
StandardsIEC 60269-1 IEC 60947-3 IEC 60269-2

Product details

The GS1LG4 is a TeSys GS fuse switch disconnector body — the base unit that accepts the fuse carrier and operating handle to make a complete disconnecting switch. It is a 4-pole, DIN-rail-mounted device rated for 160 A at 400 V AC in AC-23B duty, which means it handles motor loads with occasional inrush (switching of motors or other highly inductive loads). The breaking capacity is 1280 A at 400 V AC-23B, and the making capacity is 1600 A at the same voltage and duty — so it can close onto a fault without welding contacts. It meets IEC 60269-1, IEC 60947-3, and IEC 60269-2 standards for fuse-links and switch-disconnectors.

For DC applications, it carries 125 A at 440 V with two poles in series per phase.

This part is marked obsolete by the manufacturer. There is no listed direct successor in the evidence.

Mounts on DIN rail via the rail plate. The operating handle can be fitted on the external right side or external front.

Durability and environmental

Mechanical durability is 10,000 cycles; electrical durability is 1,000 cycles in AC-23A/B and 200 cycles in DC-23A/B. The fuse cover passes the glow-wire test at 850 °C, and the body at 960 °C (IEC 60695-2-1), so it meets fire-resistance requirements for panel interiors. Network frequency is 50/60 Hz, and the device works on both AC and DC networks.

Frequently asked questions

What standards does the GS1LG4 comply with?

It complies with IEC 60269-1 (low-voltage fuses), IEC 60947-3 (switch-disconnectors), and IEC 60269-2 (supplemental fuse requirements). The fuse cover and body also meet IEC 60695-2-1 glow-wire test at 850 °C and 960 °C respectively.

MPN