Skip to main content
Schneider Electric GS2QQ3

Schneider GS2QQ3 Breaker Accessory

MPNGS2QQ3
Active

GS2QQ3 by SQUARE D

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

GS2QQ3 key specifications
ParameterValue
Fuse typeDIN
Network typeDC AC
Type of operating handleExternal frontal External right side
Product or component typeSwitch-disconnector-fuse
Contacts type and composition3 NO
Short-circuit withstand40 kA
Voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Breaking capacity3200 A at 400 V (AC-23B)
[Ie] rated operational current200 A at 440 V 2 poles in series per phase with terminal covers DC-23A 315 A at 440 V 2 poles in series per phase with terminal covers DC-23B 250 A at 690 V AC-23A 315 A at 500 V AC-23A 315 A at 500 V AC-23B 400 A at 400 V AC-23A 400 A at 400 V AC-23B
[Icm] rated short-circuit making capacity50 kA at 400 V with protection by gG fuses
[Ith] conventional free air thermal current400 A (at 40 °C)

All specifications

GS2QQ3 additional specifications
ParameterValue
Rated operational power in220 kW at 690 V 220 kW at 500 V 220 kW at 400 V 95 kW at 690 V
Network frequency50/60 Hz
Poles description3P
Protected poles description3t
IP degree of protectionIP20 conforming to IEC 60529 (with terminal cover)
Mounting supportPlate
Connections - terminalsPower circuit: bars 45 mm² Power circuit: lugs-ring terminals 185...240 mm²
Depth149 mm
Width252 mm
Height205 mm
Electrical durability1000 cycles AC-23A 1000 cycles AC-23B 200 cycles DC-23A 200 cycles DC-23B
Mechanical durability10000 cycles
StandardsIEC 60947-3
RangeTeSys
Fuse size2
Fire resistance850 °C fuse cover conforming to IEC 60695-2-1 960 °C body conforming to IEC 60695-2-1
Making capacity4000 A at 400 V AC-23B
Device short nameGS2Q
Tightening torquePower circuit: 25 N.m
Ambient air temperature for storage-40...80 °C
Ambient air temperature for operation-20...70 °C
MPN
GS2QQ3