Skip to main content
Schneider Electric GV2DM102BD — Miniature Circuit Breakers (MCB)

GV2DM102BD TeSys Deca DOL Motor Starter, 0.16-0.25 A, 24 V D

MPNGV2DM102BD
Obsolete

Schneider Electric TeSys Deca GV2DM102BD, DOL non-reversing motor starter, 0.16…0.25 A thermal adjustment, 24 V DC coil, 3-pole, Type 1 coordination.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2DM102BD — Identification
ParameterValue
Product range (series)TeSys Deca
Product/component typeMotor starter
GV2DM102BD — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DM102BD — Mechanical
ParameterValue
Width45 mm
Height176.4 mm
Depth99.6 mm
GV2DM102BD — Other specifications
ParameterValue
Motor power0.06 kW at 400/415 V AC 50/60 Hz 0.06 kW at 440 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2DM
Device composition1 3-pole contactor 1 motor circuit breaker type GV2ME 1 combination block GV2AF3
Motor starter typeNon reversing
Breaking capacityIq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 50 kA at 440 V conforming to IEC 60947-4-1 Iq 50 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current2.4 A
Coil voltage24 V DC
Thermal protection adjustment range0.16...0.25 A

Product details

The GV2DM102BD is a TeSys Deca direct-on-line (DOL) motor starter from Schneider Electric, combining a 3-pole contactor, a GV2ME motor circuit breaker, and a GV2AF3 combination block in one assembly. It is a non-reversing starter rated for AC-3 utilization, meaning it is designed for starting and stopping squirrel-cage induction motors under load — the standard duty for conveyor, pump, and fan drives. The thermal protection adjustment range of 0.16…0.25 A sets the overload trip point for the connected motor. This is the spec that decides fit: if your motor full-load current falls outside that window, this starter cannot protect it. The magnetic trip is fixed at 2.4 A, clearing short-circuit faults upstream of the overload curve.

Rated breaking capacity is 50 kA at 400/415 V, 440 V, and 500 V, all conforming to IEC 60947-4-1. Type 1 coordination means the starter is not expected to remain serviceable after a fault at its maximum rating; the contactor and breaker may need replacement, but the rest of the panel is protected.

The GV2DM102BD measures 45 mm wide, 99.6 mm deep, and 176.4 mm tall. Depth of 99.6 mm means it clears most 120 mm deep enclosures, but verify clearance for wiring ducts and the combination block projection.

Frequently asked questions

Where can I buy GV2DM102BD?

The GV2DM102BD is available to source through independent distribution on a quoted-to-order basis. Availability and current pricing are confirmed at quote time against an RFQ. No stock or lead-time figures are held on this listing.

What is the thermal adjustment range on GV2DM102BD?

The thermal protection adjustment range is 0.16…0.25 A. The magnetic trip is fixed at 2.4 A. The motor full-load current must fall within the thermal window for the overload to protect correctly.

What is the breaking capacity of GV2DM102BD?

Rated breaking capacity is 50 kA at 400/415 V, 440 V, and 500 V, per IEC 60947-4-1. This is the maximum fault current the starter can interrupt safely.

MPN
GV2DM102BD