The GV2DM102F7 is a non-reversing DOL combination starter from the TeSys Deca family, integrating a GV2ME motor circuit breaker and a 3-pole contactor in one block with a GV2AF3 auxiliary contact block. Its thermal protection adjustment range of 0.16…0.25 A makes it suited for very small motor loads — think fractional-horsepower pumps, small fans, or conveyor drives below 0.06 kW at 400/415 V AC. Rated breaking capacity hits 50 kA at 400/415 V (IEC 60947-4-1), so it can clear a bolted fault on a 50 kA available fault-current bus without upstream coordination worries — Type 1 coordination means the starter may need replacement after a fault, but the downstream motor stays protected. The magnetic tripping threshold is fixed at 2.4 A, which triggers instantaneously on short-circuit; the thermal bimetallic element handles the 0.16…0.25 A overload band. That narrow window means this part is not a general-purpose breaker — it is sized specifically for the motor's full-load current.
The 0.06 kW motor power rating at 400/415 V AC (50/60 Hz) and 0.06 kW at 440 V AC is the headline selection parameter — this starter is for sub-0.1 kW motors only. The 110 V AC coil voltage means the control circuit must supply 110 V AC; verify your panel's control transformer voltage before specifying. Dimensions (176.4 mm height, 45 mm width, 99.6 mm depth) fit a standard DIN-rail footprint. The 45 mm width is typical for a 3-pole motor starter in the TeSys Deca range.