Skip to main content
Schneider Electric GV2DM106BD — Miniature Circuit Breakers (MCB)

Schneider Electric GV2DM106BD TeSys Deca DOL Starter, 1-1.6A

MPNGV2DM106BD
Active

Schneider Electric TeSys Deca DOL combination starter, GV2DM106BD, 1...1.6 A thermal protection range, 24 V DC coil, 3-pole, non-reversing, AC-3 utilisation category.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2DM106BD — Identification
ParameterValue
Product range (series)TeSys Deca
Product/component typeMotor starter
GV2DM106BD — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DM106BD — Mechanical
ParameterValue
Width45 mm
Height176.4 mm
Depth99.6 mm
GV2DM106BD — Other specifications
ParameterValue
Motor power0.55 kW at 400/415 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2DM
Device composition1 motor circuit breaker type GV2ME 1 combination block GV2AF3 1 3-pole contactor
Motor starter typeNon reversing
Breaking capacityIq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 50 kA at 440 V conforming to IEC 60947-4-1 Iq 50 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current22.5 A
Coil voltage24 V DC
Thermal protection adjustment range1...1.6 A

Product details

It provides thermal protection adjustable from 1 to 1.6 A and magnetic tripping at 22.5 A, covering small motor loads up to 0.55 kW at 400/415 V AC or 0.75 kW at 500 V AC.

Rated in utilisation category AC-3 (squirrel-cage motor starting), the GV2DM106BD carries a breaking capacity of Iq 50 kA at 400/415 V, 440 V, and 500 V per IEC 60947-4-1 — sufficient to interrupt fault currents up to that level without upstream damage, provided the installation's prospective short-circuit current stays within that limit. The 24 V DC control coil suits safety circuits or PLC-driven panels where 24 VDC is the standard control voltage. The 1...1.6 A thermal adjustment range means this starter is sized for fractional-horsepower motors — a 0.55 kW pump or fan on 400 V, for example.

Deployment context

Depth of 99.6 mm and height of 176.4 mm mean it fits in shallow enclosures — check clearance if a door-mounted operator station sits behind the panel.

Frequently asked questions

What are the key dimensions of the GV2DM106BD?

Width is 45 mm, depth is 99.6 mm, and height is 176.4 mm. The 45 mm width matches standard modular DIN-rail spacing.

What motor power does the GV2DM106BD cover?

At 400/415 V AC it covers 0.55 kW motors; at 440 V AC it covers 0.55 kW; at 500 V AC it covers 0.37 kW, 0.55 kW, or 0.75 kW depending on the specific rating. The thermal adjustment range is 1 to 1.6 A.

What control voltage does the GV2DM106BD use?

The control coil operates on 24 V DC.

MPN
GV2DM106BD