It provides thermal protection adjustable from 1 to 1.6 A and magnetic tripping at 22.5 A, covering small motor loads up to 0.55 kW at 400/415 V AC or 0.75 kW at 500 V AC.
Rated in utilisation category AC-3 (squirrel-cage motor starting), the GV2DM106BD carries a breaking capacity of Iq 50 kA at 400/415 V, 440 V, and 500 V per IEC 60947-4-1 — sufficient to interrupt fault currents up to that level without upstream damage, provided the installation's prospective short-circuit current stays within that limit. The 24 V DC control coil suits safety circuits or PLC-driven panels where 24 VDC is the standard control voltage. The 1...1.6 A thermal adjustment range means this starter is sized for fractional-horsepower motors — a 0.55 kW pump or fan on 400 V, for example.
Deployment context
Depth of 99.6 mm and height of 176.4 mm mean it fits in shallow enclosures — check clearance if a door-mounted operator station sits behind the panel.