Skip to main content
Schneider Electric GV2DM108Q7 — Miniature Circuit Breakers (MCB)

Schneider GV2DM108Q7 TeSys Deca Motor Starter, 2.5-4A, Obsol

MPNGV2DM108Q7
Obsolete

Schneider Electric TeSys Deca GV2DM108Q7, DOL non-reversing motor starter, 2.5...4 A thermal protection, 380 VAC 50/60 Hz coil, 3-pole, Type 1 coordination.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2DM108Q7 — Identification
ParameterValue
Product range (series)TeSys Deca
Product/component typeMotor starter
GV2DM108Q7 — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DM108Q7 — Mechanical
ParameterValue
Width45 mm
Height176.4 mm
Depth99.6 mm
GV2DM108Q7 — Other specifications
ParameterValue
Motor power1.1 kW at 400/415 V AC 50/60 Hz 1.5 kW at 400/415 V AC 50/60 Hz 1.5 kW at 440 V AC 50/60 Hz 1.5 kW at 500 V AC 50/60 Hz 2.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2DM
Device composition1 motor circuit breaker type GV2ME 1 combination block GV2AF3 1 3-pole contactor
Motor starter typeNon reversing
Breaking capacityIq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 50 kA at 440 V conforming to IEC 60947-4-1 Iq 50 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current51 A
Thermal protection adjustment range2.5...4 A

Product details

The Schneider GV2DM108Q7 is a DOL (direct-on-line) non-reversing motor starter from the TeSys Deca range, combining a GV2ME motor circuit breaker, a GV2AF3 combination block, and a 3-pole contactor into one assembled unit. Its thermal protection adjustment range of 2.5...4 A sets the overload relay to match the motor's full-load current — set it to the motor nameplate FLA within that window. Rated for AC-3 utilization (squirrel-cage motor starting), it handles the inrush and switching duty of induction motors up to 1.5 kW at 400/415 V or 2.5 kW at 500 V. The magnetic trip is fixed at 51 A, providing instantaneous short-circuit protection that clears faults before the contactor welds.

Rated breaking capacity is 50 kA at 400/415 V, 440 V, and 500 V per IEC 60947-4-1 — that is the fault current the starter can safely interrupt without external fuses, given Type 1 coordination (the starter may need contactor replacement after a fault, but the downstream circuit is protected). Panel footprint: 45 mm wide, 176.4 mm tall, 99.6 mm deep — fits a standard 45 mm DIN-rail slot; the depth includes the overhang of the combination block and contactor.

The GV2DM108Q7 is listed as Obsolete by Schneider Electric.

Frequently asked questions

Where can I buy GV2DM108Q7?

It is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the thermal adjustment range for GV2DM108Q7?

The thermal protection adjustment range is 2.5...4 A.

What is the breaking capacity of GV2DM108Q7?

Rated breaking capacity is 50 kA at 400/415 V, 440 V, and 500 V per IEC 60947-4-1.

MPN
GV2DM108Q7