Skip to main content
Schneider Electric GV2DM114B7 — Miniature Circuit Breakers (MCB)

Schneider GV2DM114B7 TeSys Deca DOL Starter, 6-10A, 24V AC

MPNGV2DM114B7
Obsolete

Schneider Electric TeSys Deca GV2DM114B7, DOL combination starter, 6…10 A thermal adjustment, 24 V AC 50/60 Hz coil, 3-pole, AC-3 utilisation category.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2DM114B7 — Identification
ParameterValue
Product range (series)TeSys Deca
Product/component typeMotor starter
GV2DM114B7 — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DM114B7 — Mechanical
ParameterValue
Width45 mm
Height176.4 mm
Depth99.6 mm
GV2DM114B7 — Other specifications
ParameterValue
Motor power3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2DM
Device composition1 combination block GV2AF3 1 3-pole contactor 1 motor circuit breaker type GV2ME
Motor starter typeNon reversing
Breaking capacityIq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 15 kA at 440 V conforming to IEC 60947-4-1 Iq 6 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current138 A
Coil voltage24 V AC 50/60 Hz
Thermal protection adjustment range6...10 A

Product details

The GV2DM114B7 is a direct-on-line (DOL) combination motor starter from the Schneider TeSys Deca range. It packages a 3-pole contactor and a motor circuit breaker (type GV2ME) into one block with a GV2AF3 combination base, so you get short-circuit and overload protection plus switching in a single DIN-rail footprint. The thermal protection adjustment range is 6…10 A, and the magnetic trip is fixed at 138 A. That means for a motor drawing, say, 8 A full-load, you dial the thermal dial to match and the magnetic element handles the start-up inrush without nuisance tripping. Rated for AC-3 duty (squirrel-cage motor starting), the unit carries motor power ratings from 3 kW at 400/415 V up to 5.5 kW at 500 V.

Rated breaking capacity (Iq) is 50 kA at 400/415 V per IEC 60947-4-1, dropping to 15 kA at 440 V and 6 kA at 500 V. This is Type 1 coordination — meaning after a fault the starter may need component replacement, but the installation stays safe. For a 400 V line with high available fault current, that 50 kA figure gives solid headroom.

Physical fit

Dimensions are 45 mm wide, 176.4 mm high, and 99.6 mm deep — a standard TeSys Deca footprint that snaps onto DIN rail. The 45 mm width (3-module) fits typical panel layouts without crowding adjacent devices.

Frequently asked questions

What are the key ratings for the GV2DM114B7?

Thermal protection adjustment 6…10 A, magnetic trip 138 A, AC-3 utilisation category, control voltage 24 V AC 50/60 Hz, and breaking capacity 50 kA at 400/415 V per IEC 60947-4-1.

What is the physical size of the GV2DM114B7?

Width 45 mm, height 176.4 mm, depth 99.6 mm — a standard 3-module TeSys Deca DIN-rail footprint.

What motor power does the GV2DM114B7 support?

Up to 3 kW at 400/415 V, 4 kW at 440 V, and 5.5 kW at 500 V, all at 50/60 Hz, AC-3 duty.

MPN
GV2DM114B7