Skip to main content
Schneider Electric GV2DM132B7 — Molded Case Circuit Breakers (MCCB)

TeSys Deca GV2DM132B7 Motor Starter, 24-32A, 24V AC, Obsolet

MPNGV2DM132B7
Obsolete

TeSys Deca GV2DM132B7, DOL combination motor starter, 24-32 A thermal adjustment, 24 V AC 50/60 Hz coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2DM132B7 — Identification
ParameterValue
Product / component typeMotor starter
GV2DM132B7 — Mechanical
ParameterValue
Height186.8 mm
Width45 mm
Depth105.9 mm
GV2DM132B7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2DM
GV2DM132B7 — Other specifications
ParameterValue
Motor power15 kW at 400/415 V AC 50/60 Hz 15 kW at 440 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz
Range of productTeSys Deca
Coordination typeType 1
Device composition1 motor circuit breaker type GV2ME 1 combination block GV2AF3 1 3-pole contactor
Motor starter typeNon reversing
Utilisation categoryAC-3
Breaking capacityIq 10 kA at 400/415 V conforming to IEC 60947-4-1 Iq 6 kA at 440 V conforming to IEC 60947-4-1 Iq 4 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current416 A
Coil voltage24 V AC 50/60 Hz
Thermal protection adjustment range24...32 A

Product details

The GV2DM132B7 is a non-reversing DOL combination starter from the TeSys Deca range, integrating a GV2ME motor circuit breaker, a GV2AF3 combination block, and a 3-pole contactor in one unit. It provides thermal protection adjustable from 24 to 32 A and is rated for AC-3 utilization category, meaning it is designed for starting and stopping squirrel-cage motors under load. The magnetic trip is set at 416 A, clearing short circuits before the contactor welds.

Rated breaking capacity (Iq) is 10 kA at 400/415 V per IEC 60947-4-1, dropping to 6 kA at 440 V and 4 kA at 500 V. This is a Type 1 coordination — after a fault the starter may need component replacement, but it will not cause a fire or shock hazard. For a panel builder, that means the upstream protection (fuse or MCCB) must be selected to keep fault energy within this curve, or step up to a Type 2 coordinated assembly if production uptime demands it.

Motor power coverage

The unit covers 15 kW at 400/415 V and 440 V, and 18.5 kW at 500 V — all at 50/60 Hz. The 24 V AC control coil matches common control transformer outputs in industrial panels, but note it is AC only; a DC coil variant would be a different order code.

Physical integration

Dimensions are 186.8 mm high, 45 mm wide, and 105.9 mm deep. Height is the main constraint when fitting into shallow enclosures or gland-plate clearance zones.

Frequently asked questions

What are the key ratings for the GV2DM132B7?

Thermal protection adjustment range is 24-32 A, magnetic trip is 416 A, and breaking capacity is 10 kA at 400/415 V (AC-3 duty). Control voltage is 24 V AC 50/60 Hz.

How do I source the GV2DM132B7 given it is obsolete?

Submit an RFQ with your target quantity. We will check our surplus and distributor network for available units. There is no direct factory lead time since production has ended.

MPN
GV2DM132B7