Skip to main content
Schneider Electric GV2DM232M7 — Molded Case Circuit Breakers (MCCB)

Schneider Electric GV2DM232M7 TeSys Deca Reversing Motor Sta

MPNGV2DM232M7
Obsolete

Schneider Electric TeSys Deca reversing motor starter, GV2DM232M7, 24-32 A thermal protection, 220 V AC 50/60 Hz coil, 3-pole, AC-3 utilization category.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2DM232M7 — Identification
ParameterValue
Product / component typeMotor starter
GV2DM232M7 — Mechanical
ParameterValue
Height186.8 mm
Width90 mm
Depth105.9 mm
GV2DM232M7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2DM
GV2DM232M7 — Other specifications
ParameterValue
Motor power15 kW at 400/415 V AC 50/60 Hz 15 kW at 440 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz
Range of productTeSys TeSys Deca
Coordination typeType 1
Device composition1 3-pole reversing contactor 1 combination block GV2AF3 1 motor circuit breaker type GV2ME
Motor starter typeReversing
Utilisation categoryAC-3
Breaking capacityIq 10 kA at 400/415 V conforming to IEC 60947-4-1 Iq 6 kA at 440 V conforming to IEC 60947-4-1 Iq 4 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current416 A
Coil voltage220 V AC 50/60 Hz
Thermal protection adjustment range24...32 A

Product details

The GV2DM232M7 is a TeSys Deca reversing motor starter combination — a single assembly integrating a 3-pole reversing contactor, a GV2AF3 combination block, and a GV2ME motor circuit breaker. The thermal protection adjustment range of 24...32 A sets the motor FLC it can protect; the magnetic trip is fixed at 416 A, providing instantaneous short-circuit protection. For a 24-32 A motor, that magnetic threshold sits above the starting inrush so nuisance trips are avoided. Rated in AC-3 duty (squirrel-cage motor switching), it delivers 15 kW at 400/415 V and 440 V, and 18.5 kW at 500 V. The breaking capacity meets IEC 60947-4-1: 10 kA at 400/415 V, 6 kA at 440 V, and 4 kA at 500 V. Coordination is Type 1, meaning after a fault the starter may need contact replacement but the breaker and contactor remain functional.

Schneider Electric lists the GV2DM232M7 as obsolete.

Mounts on a DIN rail. The 90 mm width occupies three standard 18 mm module spaces; overall depth is 105.9 mm and height 186.8 mm. The reversing contactor and breaker are pre-assembled, so the installer only needs to land the motor and control wiring — no on-site build of the reversing pair.

Frequently asked questions

What replaces GV2DM232M7?

No official successor order code is recorded in the lifecycle entry. For a direct replacement, sourcing the original code through independent distribution against an RFQ is the standard path.

What are the key ratings of GV2DM232M7?

Thermal protection adjustment 24...32 A, magnetic trip 416 A, motor power 15 kW at 400/415 V, breaking capacity 10 kA at 400/415 V (IEC 60947-4-1), control voltage 220 V AC 50/60 Hz.

Where can I buy GV2DM232M7?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
GV2DM232M7