The Schneider GV2DP220M7 is a TeSys Deca reversing motor starter combination — a pre-assembled block of one GV2P motor circuit breaker, one 3-pole reversing contactor, and one GV2AF3 combination block. The thermal protection adjustment range of 13...18 A sets the overload relay window, and the magnetic tripping current is fixed at 223 A for short-circuit protection.
Rated breaking capacity hits 50 kA at 400/415 V (per IEC 60947-4-1), which gives solid fault-clearing headroom for most industrial motor branch circuits. Motor power rating is 7.5 kW at 400/415 V and 9 kW at 440 V — so it covers a standard 7.5 kW reversing application on a 400 V three-phase supply.
Panel footprint: 90 mm wide, 186.8 mm tall, 111.9 mm deep. That's a standard TeSys Deca form factor — fits the same DIN-rail or screw-mount pattern as the rest of the GV2P family. The reversing contactor adds width over a non-reversing starter, so check your enclosure gland plate clearance before committing the layout.