Skip to main content
Schneider Electric GV2DP222P7 — Miniature Circuit Breakers (MCB)

Schneider GV2DP222P7 TeSys Deca Reversing Motor Starter, 20-

MPNGV2DP222P7
Obsolete

Schneider Electric TeSys Deca reversing motor starter combination, GV2DP222P7, 20-25 A thermal protection, 230 V AC 50/60 Hz coil, 3-pole, Type 2 coordination.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2DP222P7 — Identification
ParameterValue
Product range (series)TeSys TeSys Deca
Product/component typeMotor starter
GV2DP222P7 — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DP222P7 — Mechanical
ParameterValue
Width90 mm
Height186.8 mm
Depth111.9 mm
GV2DP222P7 — Other specifications
ParameterValue
Motor power11 kW at 400/415 V AC 50/60 Hz 15 kW at 500 V AC 50/60 Hz
Coordination typeType 2
Device short nameGV2DP
Device composition1 motor circuit breaker type GV2P 1 3-pole reversing contactor 1 combination block GV2AF3
Motor starter typeReversing
Breaking capacityIq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 20 kA at 440 V conforming to IEC 60947-4-1 Iq 10 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current327 A
Coil voltage230 V AC 50/60 Hz
Thermal protection adjustment range20...25 A

Product details

The Schneider Electric GV2DP222P7 is a TeSys Deca reversing motor starter combination — a pre-assembled unit pairing a GV2P motor circuit breaker (3-pole) with a 3-pole reversing contactor on a GV2AF3 combination block. It is rated for AC-3 duty, the utilization category for squirrel-cage motors, and carries a thermal protection adjustment range of 20 to 25 A, which sets the overload trip threshold for the connected motor.

The 20-25 A thermal adjustment range governs the motor full-load current the starter protects. For a 400/415 V supply, this maps to a motor power rating of 11 kW; at 500 V the same starter handles 15 kW. The magnetic trip is fixed at 327 A, which clears short-circuit faults without waiting for the thermal bimetal. Type 2 coordination means that under a short-circuit fault the starter remains serviceable — no welding of contactor tips, no replacement of the breaker — which reduces downtime in production-critical motor circuits.

Physical integration

The assembly occupies a 90 mm width on the DIN rail, with a depth of 111.9 mm and height of 186.8 mm. The 3-pole form factor matches standard motor feeder layouts in control panels.

Frequently asked questions

What is GV2DP222P7's thermal protection range?

The thermal protection adjustment range is 20 to 25 A, which sets the overload trip point for the motor.

What motor power does GV2DP222P7 support?

At 400/415 V AC 50/60 Hz it supports 11 kW; at 500 V AC 50/60 Hz it supports 15 kW.

MPN