Schneider Electric GV2DP222B7 — Miniature Circuit Breakers (MCB)

Schneider GV2DP222B7 TeSys Deca Reversing Motor Starter, 20-

MPNGV2DP222B7
Obsolete

Schneider Electric TeSys Deca reversing motor starter combination, GV2DP222B7, 20 to 25A thermal protection, 24VAC 50/60Hz coil, Type 2 coordination, 3-pole.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2DP222B7 — Identification
ParameterValue
Product range (series)TeSys TeSys Deca
Product/component typeMotor starter
GV2DP222B7 — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DP222B7 — Mechanical
ParameterValue
Width90 mm
Height186.8 mm
Depth111.9 mm
GV2DP222B7 — Other specifications
ParameterValue
Motor power11 kW at 400/415 V AC 50/60 Hz 15 kW at 500 V AC 50/60 Hz
Coordination typeType 2
Device short nameGV2DP
Device composition1 combination block GV2AF3 1 3-pole reversing contactor 1 motor circuit breaker type GV2P
Motor starter typeReversing
Breaking capacityIq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 20 kA at 440 V conforming to IEC 60947-4-1 Iq 10 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current327 A
Coil voltage24 V AC 50/60 Hz
Thermal protection adjustment range20...25 A

Product details

The GV2DP222B7 is a TeSys Deca reversing motor starter combination from Schneider Electric — a pre-assembled block that pairs a GV2P motor circuit breaker with a reversing contactor and a GV2AF3 combination block, all on a 3-pole chassis. Thermal protection adjusts from 20 to 25 A, and the coil pulls 24 VAC at 50/60 Hz. The AC-3 utilisation category means it's rated for switching squirrel-cage motors under full load, not just resistive heaters.

Breaking capacity is rated Iq 50 kA at 400/415 V per IEC 60947-4-1, stepping down to 20 kA at 440 V and 10 kA at 500 V. That's the fault current the starter can safely interrupt — useful for panel builders sizing upstream protection. The magnetic trip is fixed at 327 A, so the instant-trip threshold sits well above the 20–25 A thermal band to handle motor inrush without nuisance trips.

Dimensions: 90 mm wide, 186.8 mm tall, 111.9 mm deep. The 111.9 mm depth means it clears most 120 mm-deep enclosures, but check gland-plate clearance if the backplane has deep terminal blocks behind it.

Motor power rating: 11 kW at 400/415 V AC 50/60 Hz, 15 kW at 500 V AC 50/60 Hz. That's the load it can start and run in AC-3 duty — a 15 kW motor on a 500 V line, or an 11 kW on a 400 V supply. Type 2 coordination means that under a short-circuit fault, the starter remains usable after replacing the breaker — no contactor welding that forces a full swap.

Frequently asked questions

Where can I buy GV2DP222B7?

Through independent distribution channels — surplus, new-old-stock, or broker inventory. It is sourced and quoted to order against an RFQ, with availability and current pricing confirmed at quote time.

What is the thermal protection range on GV2DP222B7?

20 to 25 A, set via the dial on the motor circuit breaker section of the combination block.

What coil voltage does GV2DP222B7 use?

24 VAC at 50/60 Hz. The control circuit must supply that voltage to energise the reversing contactor coil.

What is the breaking capacity of GV2DP222B7?

Iq 50 kA at 400/415 V, 20 kA at 440 V, and 10 kA at 500 V, all per IEC 60947-4-1.