Skip to main content
Schneider Electric GV2LC0206R — Miniature Circuit Breakers (MCB)

TeSys GV2LC0206R Enclosed DOL Starter, 1.6 A, IP54

MPNGV2LC0206R
Active

TeSys GV2-LC enclosed DOL starter, GV2LC0206R, 1.6 A thermal protection, 3-pole non-reversing, IP54 polycarbonate enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2LC0206R — Identification
ParameterValue
Product range (series)TeSys
Product/component typeEnclosed DOL starter
GV2LC0206R — Ratings
ParameterValue
Poles configuration3P
Breaking capacity100 kA Icu at 220...230 V conforming to IEC 60947-2 100 kA Icu at 400...415 V conforming to IEC 60947-2 100 kA Icu at 440 V conforming to IEC 60947-2 100 kA Icu at 500 V conforming to IEC 60947-2
Rated operational voltage (Ue)690 V
GV2LC0206R — Protection
ParameterValue
Trip unit technologyMagnetic
GV2LC0206R — Mechanical
ParameterValue
Control typeRotary handle red
Width88 mm
Height166 mm
Depth173 mm
GV2LC0206R — Environmental
ParameterValue
IP degree of protectionIP54 conforming to IEC 60529
GV2LC0206R — Approvals
ParameterValue
StandardsIEC 60439-1 IEC 60947-4 EN 60947 VDE 0660-102

Product details

The TeSys GV2LC0206R is an enclosed direct-on-line (DOL) starter — a self-contained unit combining a circuit breaker and a magnetic trip in a single polycarbonate box. It's built for a fixed 1.6 A thermal protection setting, so it's sized to a specific motor FLA, not adjustable in the field. The IP54 rating (IEC 60529) tells you it's dust-protected and splash-proof — fine for a washdown area or a dusty panel, but not submersion. The polycarbonate enclosure won't corrode in a humid environment, and the rotary red handle gives a visible OFF position that can be padlocked (up to three 8 mm padlocks) for lockout/tagout.

This is a surface-mount enclosure, not DIN-rail — it bolts to a backplate or machine frame. The cable entries are pre-cut: two 20 mm and two 25 mm knockouts at both top and bottom, so you run your motor and line cables in without drilling. Dimensions are 166 mm high, 88 mm wide, 173 mm deep — it's a compact brick that fits in a standard small enclosure or on a machine pedestal. The 3-pole design handles three-phase motors up to 690 V rated operational voltage. It's non-reversing, so if you need forward/reverse, you'd pair it with an external contactor or use a different starter. The magnetic trip unit responds to short-circuit currents, while the thermal element (fixed at 1.6 A) protects against overload — no separate overload relay needed.

Frequently asked questions

What are the key ratings for this starter?

Thermal protection is fixed at 1.6 A. Breaking capacity is 100 kA at 220–500 V per IEC 60947-2. Rated operational voltage is 690 V. Enclosure is IP54.

What cable entries does the enclosure have?

It has four knockouts: two 20 mm and two 25 mm at both top and bottom, so you can bring in motor and line cables without extra drilling.

Can this starter be locked out for maintenance?

Yes, the red rotary handle accepts up to three 8 mm padlocks in the OFF position for lockout/tagout.

MPN