Skip to main content
Schneider Electric GV2LC0207R — Molded Case Circuit Breakers (MCCB)

Schneider TeSys GV2LC0207R Enclosed DOL Starter, 2.5 A

MPNGV2LC0207R
Obsolete

Schneider Electric TeSys GV2-LC enclosed DOL starter, GV2LC0207R, 2.5 A thermal protection, 3-pole, IP54, 100 kA breaking capacity.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2LC0207R — Identification
ParameterValue
Product / component typeEnclosed DOL starter
GV2LC0207R — Mechanical
ParameterValue
Height166 mm
Width88 mm
Depth173 mm
GV2LC0207R — Electrical
ParameterValue
Breaking capacity100 kA Icu at 220...230 V conforming to IEC 60947-2 100 kA Icu at 400...415 V conforming to IEC 60947-2 100 kA Icu at 440 V conforming to IEC 60947-2 100 kA Icu at 500 V conforming to IEC 60947-2
[Ue] rated operational voltage690 V
GV2LC0207R — Specifications
ParameterValue
Poles description3P
Trip unit technologyMagnetic
Device short nameGV2LC
StandardsIEC 60439-1 EN 60947 IEC 60947-4 VDE 0660-102

Product details

The Schneider Electric TeSys GV2LC0207R is an enclosed direct-on-line (DOL) starter — a self-contained unit combining a circuit breaker and a magnetic trip in a single polycarbonate enclosure, rated for a 2.5 A thermal protection setting. This is the part you spec when you need a compact, IP54-rated motor starter for a small pump, fan, or conveyor that doesn't justify a separate breaker-and-contactor assembly. The IP54 rating means it's sealed against dust ingress and splashing water — suitable for installation in washdown areas or outdoor enclosures where you don't want a separate cabinet.

The headline number is the 2.5 A thermal protection adjustment range — that's the motor full-load current it's designed to protect. If your motor draws 2.3 A FLA, this starter will trip on overload at the right threshold; if your motor draws 3 A, you need the next size up. The magnetic trip (short-circuit protection) is fixed and coordinated with the thermal element, so you don't set it separately. Breaking capacity is 100 kA Icu at 400…415 V (per IEC 60947-2). In practice, unless your panel's prospective fault current is above that level, you don't need an upstream current-limiting fuse. Rated operational voltage goes up to 690 V, so it's fine on 400 V three-phase systems common in European and Asian industrial plants. The polycarbonate enclosure is rated IP54, so it handles dust and hose-down, but it's not submersible — keep it out of standing water.

Dimensions are 166 mm high × 88 mm wide × 173 mm deep — it's a compact brick that mounts directly to a backplate or inside a small enclosure. Cable entry is provided top and bottom: 2 × 20 mm ISO and 2 × 25 mm ISO knockouts at both ends, so you can route incoming supply and motor leads without drilling. The red rotary handle protrudes from the front; the enclosure is designed for surface mounting, not DIN rail.

Standards compliance includes IEC 60439-1, EN 60947, IEC 60947-4, and VDE 0660-102 — covers the main European low-voltage switchgear and motor-starter standards. For UL/CSA compliance, verify the specific listing for your jurisdiction; the evidence doesn't carry those marks.

Frequently asked questions

What are the key ratings I need to check for fit?

The thermal protection adjustment range is 2.5 A — that's the motor FLA it protects. Breaking capacity is 100 kA Icu at 400…415 V. Rated operational voltage is 690 V. Enclosure is IP54.

What standards does this starter comply with?

It complies with IEC 60439-1, EN 60947, IEC 60947-4, and VDE 0660-102.

What are the mounting dimensions and cable entry?

Dimensions are 166 mm high × 88 mm wide × 173 mm deep. Cable knockouts: 2 × 20 mm ISO and 2 × 25 mm ISO at both top and bottom.

MPN