Skip to main content
Schneider Electric GV2LC0207R — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2LC0207R Enclosed DOL Starter, 2.5 A

MPNGV2LC0207R
Active

Schneider Electric TeSys GV2-LC enclosed DOL starter, GV2LC0207R, 2.5 A thermal protection, 3-pole, IP54, 100 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2LC0207R — Identification
ParameterValue
Product range (series)TeSys
Product/component typeEnclosed DOL starter
GV2LC0207R — Ratings
ParameterValue
Poles configuration3P
Breaking capacity100 kA Icu at 220...230 V conforming to IEC 60947-2 100 kA Icu at 400...415 V conforming to IEC 60947-2 100 kA Icu at 440 V conforming to IEC 60947-2 100 kA Icu at 500 V conforming to IEC 60947-2
Rated operational voltage (Ue)690 V
GV2LC0207R — Protection
ParameterValue
Trip unit technologyMagnetic
GV2LC0207R — Mechanical
ParameterValue
Control typeRotary handle red
Width88 mm
Height166 mm
Depth173 mm
GV2LC0207R — Environmental
ParameterValue
IP degree of protectionIP54 conforming to IEC 60529
GV2LC0207R — Approvals
ParameterValue
StandardsIEC 60439-1 EN 60947 IEC 60947-4 VDE 0660-102

Product details

The Schneider Electric TeSys GV2LC0207R is an enclosed direct-on-line (DOL) starter — a self-contained unit combining a circuit breaker and a magnetic trip in a single polycarbonate enclosure, rated for a 2.5 A thermal protection setting. This is the part you spec when you need a compact, IP54-rated motor starter for a small pump, fan, or conveyor that doesn't justify a separate breaker-and-contactor assembly. The IP54 rating means it's sealed against dust ingress and splashing water — suitable for installation in washdown areas or outdoor enclosures where you don't want a separate cabinet.

The headline number is the 2.5 A thermal protection adjustment range — that's the motor full-load current it's designed to protect. If your motor draws 2.3 A FLA, this starter will trip on overload at the right threshold; if your motor draws 3 A, you need the next size up. The magnetic trip (short-circuit protection) is fixed and coordinated with the thermal element, so you don't set it separately. Breaking capacity is 100 kA Icu at 400…415 V (per IEC 60947-2). In practice, unless your panel's prospective fault current is above that level, you don't need an upstream current-limiting fuse. Rated operational voltage goes up to 690 V, so it's fine on 400 V three-phase systems common in European and Asian industrial plants. The polycarbonate enclosure is rated IP54, so it handles dust and hose-down, but it's not submersible — keep it out of standing water.

Dimensions are 166 mm high × 88 mm wide × 173 mm deep — it's a compact brick that mounts directly to a backplate or inside a small enclosure. Cable entry is provided top and bottom: 2 × 20 mm ISO and 2 × 25 mm ISO knockouts at both ends, so you can route incoming supply and motor leads without drilling. The red rotary handle protrudes from the front; the enclosure is designed for surface mounting, not DIN rail.

Standards compliance includes IEC 60439-1, EN 60947, IEC 60947-4, and VDE 0660-102 — covers the main European low-voltage switchgear and motor-starter standards. For UL/CSA compliance, verify the specific listing for your jurisdiction; the evidence doesn't carry those marks.

Frequently asked questions

What are the key ratings I need to check for fit?

The thermal protection adjustment range is 2.5 A — that's the motor FLA it protects. Breaking capacity is 100 kA Icu at 400…415 V. Rated operational voltage is 690 V. Enclosure is IP54.

What standards does this starter comply with?

It complies with IEC 60439-1, EN 60947, IEC 60947-4, and VDE 0660-102.

What are the mounting dimensions and cable entry?

Dimensions are 166 mm high × 88 mm wide × 173 mm deep. Cable knockouts: 2 × 20 mm ISO and 2 × 25 mm ISO at both top and bottom.

MPN
GV2LC0207R