Skip to main content
Schneider Electric GV2LC0208R — Miniature Circuit Breakers (MCB)

TeSys GV2LC0208R Enclosed DOL Starter, 4 A, 100 kA Icu

MPNGV2LC0208R
Active

TeSys GV2LC, enclosed DOL starter, GV2LC0208R, 4 A thermal protection, 100 kA Icu, IP54, polycarbonate enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2LC0208R — Identification
ParameterValue
Product range (series)TeSys
Product/component typeEnclosed DOL starter
GV2LC0208R — Ratings
ParameterValue
Poles configuration3P
Breaking capacity100 kA Icu at 220...230 V conforming to IEC 60947-2 100 kA Icu at 400...415 V conforming to IEC 60947-2 100 kA Icu at 440 V conforming to IEC 60947-2 100 kA Icu at 500 V conforming to IEC 60947-2
Rated operational voltage (Ue)690 V
GV2LC0208R — Protection
ParameterValue
Trip unit technologyMagnetic
GV2LC0208R — Mechanical
ParameterValue
Control typeRotary handle red
Width88 mm
Height166 mm
Depth173 mm
GV2LC0208R — Environmental
ParameterValue
IP degree of protectionIP54 conforming to IEC 60529
GV2LC0208R — Approvals
ParameterValue
StandardsIEC 60439-1 IEC 60947-4 VDE 0660-102 EN 60947

Product details

The TeSys GV2LC0208R is an enclosed direct-on-line (DOL) starter rated for 4 A thermal protection, built into a polycarbonate enclosure with IP54 ingress protection per IEC 60529. It combines a magnetic-trip circuit breaker and a non-reversing motor starter in one package, so the line-side protection and motor switching live in a single enclosure — one part to spec, one part to mount.

The enclosure dimensions are 166 mm high, 88 mm wide, and 173 mm deep — sized for a standard industrial control panel footprint, with cable entry knockouts at 20 mm and 25 mm ISO on both top and bottom faces.

The GV2LC0208R carries compliance to IEC 60439-1, IEC 60947-4, VDE 0660-102, and EN 60947 — the key standards for motor-starter assemblies and low-voltage switchgear in European and IEC-adopting markets.

Frequently asked questions

What breaking capacity does this starter have at 400 V?

100 kA Icu at 400–415 V per IEC 60947-2, which is the same rating it carries at 220–230 V, 440 V, and 500 V.

What is the thermal protection adjustment range?

Fixed at 4 A — this is a single-setting thermal-magnetic starter, not an adjustable overload relay.

What enclosure rating does it carry?

IP54 per IEC 60529, meaning dust-protected and splash-proof — suitable for indoor industrial environments with light washdown or dust exposure.

What compliance documentation is available for this part?

The part is certified to IEC 60439-1, IEC 60947-4, VDE 0660-102, and EN 60947. RoHS and REACH declarations are standard for the TeSys range but are not individually listed in this entry.

MPN
GV2LC0208R