Skip to main content
Schneider Electric GV2LC0210 — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2LC0210 Enclosed DOL Starter, 6.3 A, 100 k

MPNGV2LC0210
Obsolete

Schneider Electric TeSys GV2-LC enclosed DOL starter, 6.3 A thermal protection, 3-pole, non-reversing, IP54 polycarbonate enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2LC0210 — Identification
ParameterValue
Product range (series)TeSys
Product/component typeEnclosed DOL starter
GV2LC0210 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity100 kA Icu at 220...230 V conforming to IEC 60947-2 100 kA Icu at 400...415 V conforming to IEC 60947-2 100 kA Icu at 440 V conforming to IEC 60947-2 100 kA Icu at 500 V conforming to IEC 60947-2
Rated operational voltage (Ue)690 V
GV2LC0210 — Protection
ParameterValue
Trip unit technologyMagnetic
GV2LC0210 — Mechanical
ParameterValue
Control typeRotary handle black
Width88 mm
Height166 mm
Depth173 mm
GV2LC0210 — Environmental
ParameterValue
IP degree of protectionIP54 conforming to IEC 60529
GV2LC0210 — Approvals
ParameterValue
StandardsVDE 0660-102 IEC 60947-4 IEC 60439-1 EN 60947

Product details

The Schneider TeSys GV2LC0210 is an enclosed direct-on-line (DOL) motor starter, combining a magnetic-trip circuit breaker and a rotary-handle disconnect in a single IP54 polycarbonate enclosure.

The IP54 rating means the polycarbonate enclosure is dust-protected and splash-proof, suitable for light industrial environments but not for washdown zones (that would require IP65 or higher). The 6.3 A fixed thermal setting limits this to a specific motor FLA — if your motor draws 5.5 A or 7.0 A, this is not the right thermal pickup; you would need a different GV2LC variant with the correct adjustment range.

Physical integration

The enclosure measures 173 mm deep, 88 mm wide, and 166 mm high. Cable entry is via ISO knockouts: two 20 mm at top and bottom, plus two 25 mm at top and bottom. The rotary handle accepts up to three 8 mm padlocks for lockout/tagout in the OFF position. The polycarbonate housing is non-metallic, so no additional earthing of the enclosure is required beyond the internal PE connection.

Frequently asked questions

What is the breaking capacity of this starter?

The breaking capacity is 100 kA Icu at 220...230 V, 400...415 V, 440 V, and 500 V, all conforming to IEC 60947-2. This high rating means it can be used on systems with high fault current without additional upstream protection.

What is the enclosure protection rating?

The enclosure is rated IP54 per IEC 60529, meaning it is protected against dust ingress and splashing water. It is suitable for indoor industrial environments but not for direct washdown or outdoor exposure without additional weather protection.

What thermal protection range does this starter cover?

The thermal protection adjustment range is fixed at 6.3 A. This is not an adjustable range — it is a single setting. The starter uses magnetic trip technology for short-circuit protection and a fixed thermal element for overload protection.

MPN
GV2LC0210