Schneider Electric GV2LC0214 — Miniature Circuit Breakers (MCB)

Schneider Electric GV2LC0214 TeSys Enclosed DOL Starter, 10

MPNGV2LC0214
Active

Schneider Electric TeSys GV2LC0214, enclosed DOL starter, 10 A thermal protection adjustment range, IP54 polycarbonate enclosure, 3-pole non-reversing with magnetic trip.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2LC0214 — Identification
ParameterValue
Product range (series)TeSys
Product/component typeEnclosed DOL starter
GV2LC0214 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity10 kA Icu at 500 V conforming to IEC 60947-2 100 kA Icu at 220...230 V conforming to IEC 60947-2 100 kA Icu at 400...415 V conforming to IEC 60947-2 20 kA Icu at 440 V conforming to IEC 60947-2
Rated operational voltage (Ue)690 V
GV2LC0214 — Protection
ParameterValue
Trip unit technologyMagnetic
Magnetic tripping limit13 x In +/- 20 %
GV2LC0214 — Mechanical
ParameterValue
Control typeRotary handle black
Width88 mm
Height166 mm
Depth173 mm
GV2LC0214 — Environmental
ParameterValue
IP degree of protectionIP54 conforming to IEC 60529
GV2LC0214 — Approvals
ParameterValue
StandardsVDE 0660-102 IEC 60947-4 IEC 60439-1 EN 60947

Product details

The Schneider Electric GV2LC0214 is an enclosed direct-on-line (DOL) starter from the TeSys range, combining a circuit breaker and magnetic trip unit in one polycarbonate enclosure. It's rated for a thermal protection adjustment range of 10 A, meaning it's sized for a motor drawing that full-load current — set the dial to match the nameplate, and the magnetic trip hits at 13 x In (±20%) for short-circuit protection. The IP54 rating (per IEC 60529) means the enclosure is dust-protected and splash-proof — not submersible, but fine for washdown areas, pump stations, or outdoor cabinets where hose spray is a risk. The polycarbonate shell won't corrode like painted steel in a wet well atmosphere, though I'd still keep it out of direct H2S off-gassing if the concentration is heavy.

Breaking capacity — what it handles

Breaking capacity varies with voltage: 100 kA Icu at 220–230 V and 400–415 V, 20 kA at 440 V, and 10 kA at 500 V, all conforming to IEC 60947-2. At 400 V three-phase — common for industrial motor circuits — the 100 kA figure gives you serious fault-clearing headroom, enough for most distribution panels without needing upstream current-limiting fuses.

Enclosure and integration details

The enclosure dimensions are 173 mm deep, 88 mm wide, and 166 mm high. Cable entries are pre-cut for ISO knockouts: two 20 mm at top and bottom, plus two 25 mm at top and bottom — enough for incoming supply and motor leads through separate glands. The black rotary handle extends through the cover for manual ON/OFF and can be padlocked in the OFF position with up to three 8 mm padlocks for lockout/tagout.

Frequently asked questions

What are the key ratings for the GV2LC0214?

Thermal protection adjustment range is 10 A, with a magnetic trip limit of 13 x In (±20%). Breaking capacity reaches 100 kA Icu at 400–415 V (IEC 60947-2). The enclosure is rated IP54 and measures 173 mm deep by 88 mm wide by 166 mm high.

What compliance standards does the GV2LC0214 meet?

It conforms to VDE 0660-102, IEC 60947-4, IEC 60439-1, and EN 60947. The IP54 rating is per IEC 60529, and breaking capacity is certified to IEC 60947-2.

What cable entries does the enclosure have?

The polycarbonate enclosure has four ISO knockouts: two 20 mm and two 25 mm at both top and bottom, giving flexibility for cable gland sizes on the supply and motor side.