Schneider Electric GV2LC0214R — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2LC0214R Enclosed DOL Starter, 10 A, IP54

MPNGV2LC0214R
Active

Schneider Electric TeSys GV2LC0214R enclosed DOL starter, 10 A thermal protection, 3-pole, IP54 polycarbonate enclosure, 100 kA breaking capacity at 400 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2LC0214R — Identification
ParameterValue
Product range (series)TeSys
Product/component typeEnclosed DOL starter
GV2LC0214R — Ratings
ParameterValue
Poles configuration3P
Breaking capacity10 kA Icu at 500 V conforming to IEC 60947-2 100 kA Icu at 220...230 V conforming to IEC 60947-2 100 kA Icu at 400...415 V conforming to IEC 60947-2 20 kA Icu at 440 V conforming to IEC 60947-2
Rated operational voltage (Ue)690 V
GV2LC0214R — Protection
ParameterValue
Trip unit technologyMagnetic
GV2LC0214R — Mechanical
ParameterValue
Control typeRotary handle red
Width88 mm
Height166 mm
Depth173 mm
GV2LC0214R — Environmental
ParameterValue
IP degree of protectionIP54 conforming to IEC 60529
GV2LC0214R — Approvals
ParameterValue
StandardsIEC 60439-1 EN 60947 IEC 60947-4 VDE 0660-102

Product details

The Schneider TeSys GV2LC0214R is an enclosed direct-on-line (DOL) starter combining a circuit breaker and magnetic trip unit in a single IP54 polycarbonate enclosure. It is rated for a 10 A thermal protection adjustment range and delivers a 100 kA breaking capacity at 400–415 V per IEC 60947-2, meaning it can safely interrupt high fault currents on a 400 V distribution system without upstream coordination issues.

The 10 A thermal protection adjustment range sets the overload trip point for the connected motor — sized for a motor drawing up to 10 A full-load current. The magnetic trip unit provides instantaneous short-circuit protection, with the 100 kA Icu at 400–415 V ensuring the starter withstands and clears severe faults without exploding or welding contacts. The IP54 rating means the enclosure is dust-protected and splash-proof, suitable for washdown areas or outdoor installations where the starter is not directly hosed. The polycarbonate housing resists corrosion and UV, making it a fit for food processing, chemical plants, or coastal environments. Cable entry accommodates up to 2 x 25 mm² ISO at the bottom and 2 x 20 mm² ISO at the top, giving flexibility for incoming supply and outgoing motor cables. The rotary red handle provides local lockout capability with up to three 8 mm padlocks in the OFF position, meeting OSHA lockout/tagout requirements.

This enclosed DOL starter is designed for controlling and protecting three-phase motors in industrial machinery, conveyors, pumps, fans, and compressors. It mounts directly on a wall or machine frame via the enclosure's integral fixing points — no separate panel or DIN rail needed. The non-reversing configuration suits applications where motor direction is fixed.

Frequently asked questions

What are the key ratings of the GV2LC0214R?

It is a 10 A enclosed DOL starter with a 100 kA breaking capacity at 400–415 V (IEC 60947-2), IP54 polycarbonate enclosure, and 3-pole magnetic trip protection.

What cable sizes fit the GV2LC0214R?

The enclosure accepts up to 2 x 25 mm² ISO cables at the bottom and 2 x 20 mm² ISO at the top for both incoming and outgoing connections.